F0004 on the Siemens MICROMASTER 430 is the “Inverter overtemperature” fault. On a fault the inverter switches off and shows the fault code; most MM430 faults use Siemens' reaction STOP II (F0012 uses STOP I). It will not run until the fault is reset.
The drive's heat sink or power devices reached their temperature limit. Heat comes from the load current and the switching frequency; it leaves through the fan and the heat sink fins, and the panel has to get rid of it.
- Code
- F0004
- Type
- Fault (stops the drive)
- Drive
- Siemens MICROMASTER 430
- Kind of fault
- Drive overtemperature
01 / Causes
What causes F0004
- Inadequate cooling.
- The ambient temperature is too high.
02 / Checks
What to check for F0004
In the order Siemens gives them.
- 01Check the pulse frequency P1800 is at its factory setting, and reset it if needed.
- 02Check the ambient temperature is within the permitted limits.
- 03Reduce the load and make sure cooling is adequate.
- 04Check the fan turns while the inverter is running.
03 / Clearing it
How to clear F0004
- Reset a fault by switching the power off and on, by pressing the Fn key on the BOP-2, or through the fault acknowledge sources P2103 and P2104.
- Fault codes are stored in r0947 (F0003 is stored as 3), with the fault value in r0949; P0952 clears the complete fault memory.
- Alarm codes are stored in r2110 (A0503 is stored as 503).
Clear it once. If F0004 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How drive overtemperature faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check that the drive's fan runs when the drive runs, and that its airflow is not blocked.
- 02Clean dust and fibre from the heat sink fins; in textile and cement plants this alone clears most of these trips.
- 03Measure the temperature inside the panel and check the panel fans and filters.
- 04Check the switching frequency against the factory setting and the load current against the drive's rating.
05 / Repair
When F0004 means a repair
A drive that overheats with a working fan, clean fins and normal load usually has a failed temperature sensor or poor contact between the power module and the heat sink.
If F0004 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.
06 / Other drives
Drive overtemperature: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F4 Inverter overtemperature · F6 Chip temperature rise exceeds critical levels · A504 Inverter overtemperature · A506 IGBT junction temperature rise warning |
| Siemens SINAMICS G120 | F30004 Inverter overtemperature · F30035 Overtemperature, intake air · F30036 Overtemperature, inside area · F30037 Rectifier overtemperature · A05000 Power Module overtemperature · A05001 Power Module overtemperature |
| Siemens SINAMICS V90 | F30004 Drive heat sink overtemperature · F30036 Internal overtemperature · A1009 Control module overtemperature · A5000 Drive heat sink overtemperature |
| Siemens MICROMASTER 440 | F0004 Inverter overtemperature · F0024 Rectifier temperature too high · A0504 Inverter overtemperature · A0506 Inverter load duty cycle · A0520 Rectifier overtemperature · A0521 Ambient temperature too high |
| Allen-Bradley PowerFlex 525 | F008 Heatsink OvrTmp · F009 CC OvrTmp |
| ABB ACS355 | F0003 DEV OVERTEMP · F0037 CB OVERTEMP · A2009 DEVICE OVERTEMP |
| Delta VFD-E | oH1 IGBT overheat · oH2 Power board overheat |
| Delta C2000 | oH1 IGBT overheating · oH2 Heatsink overheating |
| Delta ASDA-B2 | AL016 IGBT overheat |
| Hitachi WJ200 | E21 Inverter thermal trip |
| Schneider Electric Altivar ATV320 | OHF Drive overheating error · TJF IGBT overheating |
| INVT Goodrive20 (GD20) | OH1 Rectifier module overheat · OH2 Inverter module overheat |
| Yaskawa V1000 | oH Heatsink Overheat · oH1 Overheat 1 (Heatsink Overheat) |
| Yaskawa A1000 | oH Heatsink Overheat · oH1 Overheat 1 (Heatsink Overheat) · oH2 Heatsink Overheat Warning |
| Yaskawa GA500 | oH Heatsink Overheat · oH1 Heatsink Overheat · oH2 External Overheat (H1-XX=B) |
| Siemens MICROMASTER 420 | F0004 Inverter overtemperature · A0504 Inverter overtemperature |
| Siemens SINAMICS G110 | F0004 Inverter over temperature |
| INVT Goodrive200A (GD200A) | OH1 Rectifier module overheating · OH2 Inverter module overheat |
| Mitsubishi Electric FR-D700 | E.FIN Heatsink overheat |
| Danfoss VLT Micro Drive FC 51 | Alarm 29 Heat sink temperature |
07 / More codes
Other MICROMASTER 430 codes
Source
Siemens, MICROMASTER 430 Parameter List, Issue 10/06, 6SE6400-5AF00-0BP0, Section 5, Faults and Alarms.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007