AUE4 on the Delta C2000 is the “Auto-tune error 4” fault. A fault stops the drive's output. On over-current and over-voltage faults the drive closes its output gate at once and the motor coasts to a stop.
The drive's motor identification (autotune) run did not finish. The drive measures the motor to set up its control; it stopped because the motor was missing, the data entered was wrong, or a limit was reached.
- Code
- AUE4
- Type
- Fault (stops the drive)
- Drive
- Delta C2000
- Kind of fault
- Motor identification
01 / Causes
What causes AUE4
- A motor fault.
- The base frequency is set wrongly.
02 / Checks
What to check for AUE4
In the order Delta Electronics gives them.
- 01Check the motor works normally.
- 02Check Pr. 01-01.
Also in the manual
- Fault ID 148. The leakage inductance (Lsigma) measurement failed during auto-tuning.
03 / Clearing it
How to clear AUE4
- Remove the cause first. Then press STOP/RESET on the keypad, or switch on a multi-function input set to 5 (Reset).
- Most faults can be reset 5 seconds after the fault has cleared. Over-voltage faults reset only once the DC bus is below 90% of the trip level, and overheating faults only once the temperature is 10°C below it.
- Some faults can only be cleared by switching the power off: the current detection and hardware protection faults (cd1 to cd3, Hd0 to Hd3), the watchdog (WDTT), STO Loss (STL1 to STL3) and the CPU error (TRAP).
- After resetting, if the keypad returns to its main page and shows no fault after ESC, the fault is cleared.
Clear it once. If AUE4 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How motor identification faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check the motor is connected and the output contactor (if any) is closed during the run.
- 02Check the rating plate data entered in the drive and the motor connection (star or delta).
- 03Repeat the identification with the motor cold and uncoupled where possible.
05 / Repair
When AUE4 means a repair
Repeated failures on a correctly entered, healthy motor point at a winding fault or a drive measurement problem.
If AUE4 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Delta drives, and they arrive knowing what to look for.
06 / Other drives
Motor identification: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F41 Motor data identification failure |
| Siemens SINAMICS G120 | A07980 Rotary measurement activated · A07981 No enabling for rotary measurement · A07991 Motor identification activated |
| Siemens SINAMICS V90 | F7995 Motor identification failure · A7971 Angular commutation offset determination activated · A7991 Motor data identification activated |
| Siemens MICROMASTER 440 | F0041 Failure, motor data identification · F0042 Fault/error when optimizing the speed controller |
| Allen-Bradley PowerFlex 525 | F080 Autotune Failure |
| ABB ACS355 | F0011 ID RUN FAIL · A2019 ID RUN · A2025 FIRST START |
| Delta VFD-E | AUE Auto tuning error |
| Schneider Electric Altivar ATV320 | ASF Angle error · TNF Autotuning detected error |
| INVT Goodrive20 (GD20) | tE Motor autotuning fault · STo Maladjustment fault |
| Yaskawa V1000 | Er-01 Motor Data Error · Er-02 Minor Fault · Er-03 STOP Button Input · Er-04 Line-to-Line Resistance Error · Er-05 No-Load Current Error · Er-08 Rated Slip Error |
| Yaskawa A1000 | dv7 Initial Polarity Estimation Timeout · End1 Excessive V/f Setting · End2 Motor Iron-Core Saturation Coefficient · End3 Rated Current Setting Alarm · End4 Adjusted Slip Calculation Error · End5 Resistance Tuning Error |
| Yaskawa GA500 | dv7 Polarity Judge Timeout · End1 Excessive Rated Voltage Setting · End2 Iron Core Saturation Coefficient · End3 Rated Current Setting Alarm · End4 Adjusted Slip Calculation Error · End5 Resistance Tuning Error |
| Siemens MICROMASTER 420 | F0041 Failure, motor data identification · A0541 Motor data identification routine active |
| Siemens MICROMASTER 430 | F0041 Failure, motor data identification · A0541 Motor data identification routine active |
| INVT Goodrive200A (GD200A) | tE Motor autotuning fault |
| Danfoss VLT Micro Drive FC 51 | Alarm 51 AMT check Unom and Inom · Alarm 52 AMT low Inom · Alarm 53 AMT motor too big · Alarm 54 AMT motor too small · Alarm 55 AMT parameter out of range |
07 / More codes
Other C2000 codes
Source
Delta Electronics, C2000 Series User Manual, Issued edition 01, firmware V2.05 (2019-02-13), DELTA_IA-MDS_VFD-C2000_UM_EN_20190213, Chapter 14, Fault Codes and Descriptions.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007