V1000 Er-01: Motor Data Error

Er-01 on the Yaskawa V1000 is the “Motor Data Error” fault. A fault interrupts the drive's output and the motor coasts to a stop (unless set to stop another way). The drive stays inoperable until the fault is reset, and a digital output set for fault (H2-oo = E) closes.

The drive's motor identification (autotune) run did not finish. The drive measures the motor to set up its control; it stopped because the motor was missing, the data entered was wrong, or a limit was reached.

Code
Er-01
Type
Fault (stops the drive)
Drive
Yaskawa V1000
Kind of fault
Motor identification

01 / Causes

What causes Er-01

  • The motor data entered for Auto-Tuning was wrong: motor output and rated current (T1-02, T1-04), rated and no-load current (T1-04, E2-03), or base frequency and base speed (T1-05, T1-07) do not agree.

02 / Checks

What to check for Er-01

In the order Yaskawa gives them.

  1. 01Enter the correct motor data and restart Auto-Tuning.
  2. 02Check the drive and motor capacities, and correct T1-02 and T1-04.
  3. 03Check the rated and no-load currents, and correct T1-04 and E2-03.
  4. 04Set T1-05 and T1-07 to the correct values.

Also in the manual

  • When an Auto-Tuning fault is detected the motor coasts to a stop; no fault or alarm output is given.

03 / Clearing it

How to clear Er-01

  • Fix the cause, then reset with the reset key on the digital operator, or by closing and opening terminal S4, which is the fault reset input by default.
  • If neither clears it, switch off the drive's main power and switch it back on once the operator display has gone out.
  • Some faults need a condition met before they reset: oL1 cannot be reset until monitor U4-16 is below 100.

Clear it once. If Er-01 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How motor identification faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check the motor is connected and the output contactor (if any) is closed during the run.
  2. 02Check the rating plate data entered in the drive and the motor connection (star or delta).
  3. 03Repeat the identification with the motor cold and uncoupled where possible.

05 / Repair

When Er-01 means a repair

Repeated failures on a correctly entered, healthy motor point at a winding fault or a drive measurement problem.

If Er-01 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.

06 / Other drives

Motor identification: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F41 Motor data identification failure
Siemens SINAMICS G120A07980 Rotary measurement activated · A07981 No enabling for rotary measurement · A07991 Motor identification activated
Siemens SINAMICS V90F7995 Motor identification failure · A7971 Angular commutation offset determination activated · A7991 Motor data identification activated
Siemens MICROMASTER 440F0041 Failure, motor data identification · F0042 Fault/error when optimizing the speed controller
Allen-Bradley PowerFlex 525F080 Autotune Failure
ABB ACS355F0011 ID RUN FAIL · A2019 ID RUN · A2025 FIRST START
Delta VFD-EAUE Auto tuning error
Delta C2000AUE Auto-tuning error · AUE1 Auto-tune error 1 · AUE2 Auto-tune error 2 · AUE3 Auto-tune error 3 · AUE4 Auto-tune error 4
Schneider Electric Altivar ATV320ASF Angle error · TNF Autotuning detected error
INVT Goodrive20 (GD20)tE Motor autotuning fault · STo Maladjustment fault
Yaskawa A1000dv7 Initial Polarity Estimation Timeout · End1 Excessive V/f Setting · End2 Motor Iron-Core Saturation Coefficient · End3 Rated Current Setting Alarm · End4 Adjusted Slip Calculation Error · End5 Resistance Tuning Error
Yaskawa GA500dv7 Polarity Judge Timeout · End1 Excessive Rated Voltage Setting · End2 Iron Core Saturation Coefficient · End3 Rated Current Setting Alarm · End4 Adjusted Slip Calculation Error · End5 Resistance Tuning Error
Siemens MICROMASTER 420F0041 Failure, motor data identification · A0541 Motor data identification routine active
Siemens MICROMASTER 430F0041 Failure, motor data identification · A0541 Motor data identification routine active
INVT Goodrive200A (GD200A)tE Motor autotuning fault
Danfoss VLT Micro Drive FC 51Alarm 51 AMT check Unom and Inom · Alarm 52 AMT low Inom · Alarm 53 AMT motor too big · Alarm 54 AMT motor too small · Alarm 55 AMT parameter out of range

07 / More codes

Other V1000 codes

Source

Yaskawa, YASKAWA AC Drive V1000 Technical Manual, 18F, SIEP C710606 18, 6.4 Fault Detection.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

Er-01 won't clear? Get a technician who knows the V1000.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.