Goodrive20 (GD20) tE: Motor autotuning fault

tE on the INVT Goodrive20 (GD20) is the “Motor autotuning fault” fault. A fault trips the drive and lights the TRIP indicator; the drive stays stopped until the fault is reset.

The drive's motor identification (autotune) run did not finish. The drive measures the motor to set up its control; it stopped because the motor was missing, the data entered was wrong, or a limit was reached.

Code
tE
Type
Fault (stops the drive)
Drive
INVT Goodrive20 (GD20)
Kind of fault
Motor identification

01 / Causes

What causes tE

  • The motor's capacity does not suit the VFD.
  • The motor's rated parameters are set wrongly.
  • The autotuned parameters differ greatly from the standard parameters.
  • Autotuning timed out.

02 / Checks

What to check for tE

In the order INVT gives them.

  1. 01Change the VFD model.
  2. 02Set the rated parameters from the motor nameplate.
  3. 03Remove the motor's load.
  4. 04Check the motor connection and set the parameters.
  5. 05Check the upper limit frequency is above two thirds of the rated frequency.

Also in the manual

  • Over communication this fault reads as type 20.

03 / Clearing it

How to clear tE

  • Remove the cause, then reset with the keypad's STOP/RST key, through a digital input, or by switching the power off and on. Once the fault is cleared the motor can be restarted.
  • INVT's order of work: check the keypad is working; read the fault records in group P07 to see the drive's state when the fault happened; follow the table for that code; fix the cause; then reset and run.

Clear it once. If tE comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How motor identification faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check the motor is connected and the output contactor (if any) is closed during the run.
  2. 02Check the rating plate data entered in the drive and the motor connection (star or delta).
  3. 03Repeat the identification with the motor cold and uncoupled where possible.

05 / Repair

When tE means a repair

Repeated failures on a correctly entered, healthy motor point at a winding fault or a drive measurement problem.

If tE keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on INVT drives, and they arrive knowing what to look for.

06 / Other drives

Motor identification: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F41 Motor data identification failure
Siemens SINAMICS G120A07980 Rotary measurement activated · A07981 No enabling for rotary measurement · A07991 Motor identification activated
Siemens SINAMICS V90F7995 Motor identification failure · A7971 Angular commutation offset determination activated · A7991 Motor data identification activated
Siemens MICROMASTER 440F0041 Failure, motor data identification · F0042 Fault/error when optimizing the speed controller
Allen-Bradley PowerFlex 525F080 Autotune Failure
ABB ACS355F0011 ID RUN FAIL · A2019 ID RUN · A2025 FIRST START
Delta VFD-EAUE Auto tuning error
Delta C2000AUE Auto-tuning error · AUE1 Auto-tune error 1 · AUE2 Auto-tune error 2 · AUE3 Auto-tune error 3 · AUE4 Auto-tune error 4
Schneider Electric Altivar ATV320ASF Angle error · TNF Autotuning detected error
Yaskawa V1000Er-01 Motor Data Error · Er-02 Minor Fault · Er-03 STOP Button Input · Er-04 Line-to-Line Resistance Error · Er-05 No-Load Current Error · Er-08 Rated Slip Error
Yaskawa A1000dv7 Initial Polarity Estimation Timeout · End1 Excessive V/f Setting · End2 Motor Iron-Core Saturation Coefficient · End3 Rated Current Setting Alarm · End4 Adjusted Slip Calculation Error · End5 Resistance Tuning Error
Yaskawa GA500dv7 Polarity Judge Timeout · End1 Excessive Rated Voltage Setting · End2 Iron Core Saturation Coefficient · End3 Rated Current Setting Alarm · End4 Adjusted Slip Calculation Error · End5 Resistance Tuning Error
Siemens MICROMASTER 420F0041 Failure, motor data identification · A0541 Motor data identification routine active
Siemens MICROMASTER 430F0041 Failure, motor data identification · A0541 Motor data identification routine active
INVT Goodrive200A (GD200A)tE Motor autotuning fault
Danfoss VLT Micro Drive FC 51Alarm 51 AMT check Unom and Inom · Alarm 52 AMT low Inom · Alarm 53 AMT motor too big · Alarm 54 AMT motor too small · Alarm 55 AMT parameter out of range

07 / More codes

Other Goodrive20 (GD20) codes

Source

INVT, Goodrive20 Series VFD Manual, Version V2.1 (2025), Chapter 6, Fault tracking (6.2.3 VFD faults and solutions).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of INVT and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

tE won't clear? Get a technician who knows the Goodrive20 (GD20).

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.