F0041 on the Siemens MICROMASTER 420 is the “Failure, motor data identification” fault. On a fault the inverter switches off and shows the fault code (Siemens' reaction STOP II); it will not run until the fault is reset.
The drive's motor identification (autotune) run did not finish. The drive measures the motor to set up its control; it stopped because the motor was missing, the data entered was wrong, or a limit was reached.
- Code
- F0041
- Type
- Fault (stops the drive)
- Drive
- Siemens MICROMASTER 420
- Kind of fault
- Motor identification
01 / Causes
What causes F0041
- Fault value r0949 = 0: no load (the motor is missing).
- r0949 = 1: the current limit was reached during identification.
- r0949 = 2: the identified stator resistance is below 0.1% or above 100%.
- r0949 = 30: the current controller is at its voltage limit.
- r0949 = 40: the identified data set is inconsistent; at least one identification run failed.
02 / Checks
What to check for F0041
In the order Siemens gives them.
- 01For r0949 = 0, check the motor is connected to the inverter.
- 02For r0949 = 1 to 40, check the motor data in P0304 to P0311 is correct.
- 03For r0949 = 1 to 40, check the motor is connected correctly in star or delta.
Also in the manual
- The percentages are based on the motor impedance Zb = Vmot,rated / sqrt(3) / Imot,rated.
03 / Clearing it
How to clear F0041
- Reset a fault in one of three ways: switch the power off and on, press the Fn button on the BOP or AOP, or use digital input 3 (its default setting).
- Fault codes are stored in r0947 (F0003 is stored as 3), with the fault value in r0949 (0 when the fault has none), the time of the fault in r0948 and the number of stored faults in P0952.
- Alarm codes are stored in r2110 (A0503 is stored as 503).
Clear it once. If F0041 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How motor identification faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check the motor is connected and the output contactor (if any) is closed during the run.
- 02Check the rating plate data entered in the drive and the motor connection (star or delta).
- 03Repeat the identification with the motor cold and uncoupled where possible.
05 / Repair
When F0041 means a repair
Repeated failures on a correctly entered, healthy motor point at a winding fault or a drive measurement problem.
If F0041 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.
06 / Other drives
Motor identification: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F41 Motor data identification failure |
| Siemens SINAMICS G120 | A07980 Rotary measurement activated · A07981 No enabling for rotary measurement · A07991 Motor identification activated |
| Siemens SINAMICS V90 | F7995 Motor identification failure · A7971 Angular commutation offset determination activated · A7991 Motor data identification activated |
| Siemens MICROMASTER 440 | F0041 Failure, motor data identification · F0042 Fault/error when optimizing the speed controller |
| Allen-Bradley PowerFlex 525 | F080 Autotune Failure |
| ABB ACS355 | F0011 ID RUN FAIL · A2019 ID RUN · A2025 FIRST START |
| Delta VFD-E | AUE Auto tuning error |
| Delta C2000 | AUE Auto-tuning error · AUE1 Auto-tune error 1 · AUE2 Auto-tune error 2 · AUE3 Auto-tune error 3 · AUE4 Auto-tune error 4 |
| Schneider Electric Altivar ATV320 | ASF Angle error · TNF Autotuning detected error |
| INVT Goodrive20 (GD20) | tE Motor autotuning fault · STo Maladjustment fault |
| Yaskawa V1000 | Er-01 Motor Data Error · Er-02 Minor Fault · Er-03 STOP Button Input · Er-04 Line-to-Line Resistance Error · Er-05 No-Load Current Error · Er-08 Rated Slip Error |
| Yaskawa A1000 | dv7 Initial Polarity Estimation Timeout · End1 Excessive V/f Setting · End2 Motor Iron-Core Saturation Coefficient · End3 Rated Current Setting Alarm · End4 Adjusted Slip Calculation Error · End5 Resistance Tuning Error |
| Yaskawa GA500 | dv7 Polarity Judge Timeout · End1 Excessive Rated Voltage Setting · End2 Iron Core Saturation Coefficient · End3 Rated Current Setting Alarm · End4 Adjusted Slip Calculation Error · End5 Resistance Tuning Error |
| Siemens MICROMASTER 430 | F0041 Failure, motor data identification · A0541 Motor data identification routine active |
| INVT Goodrive200A (GD200A) | tE Motor autotuning fault |
| Danfoss VLT Micro Drive FC 51 | Alarm 51 AMT check Unom and Inom · Alarm 52 AMT low Inom · Alarm 53 AMT motor too big · Alarm 54 AMT motor too small · Alarm 55 AMT parameter out of range |
07 / More codes
Other MICROMASTER 420 codes
Source
Siemens, MICROMASTER 420 Parameter List, Issue 10/06, 6SE6400-5BA00-0BP0, Section 5, Faults and Alarms.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007