TNF on the Schneider Electric Altivar ATV320 is the “Autotuning detected error” fault. A detected error stops the drive until it is cleared, in the way the manual gives for that code.
The drive's motor identification (autotune) run did not finish. The drive measures the motor to set up its control; it stopped because the motor was missing, the data entered was wrong, or a limit was reached.
- Code
- TNF
- Type
- Fault (stops the drive)
- Drive
- Schneider Electric Altivar ATV320
- Kind of fault
- Motor identification
01 / Causes
What causes TNF
- A special motor, or a motor whose power does not suit the drive.
- The motor is not connected to the drive.
- The motor is not stopped.
02 / Checks
What to check for TNF
In the order Schneider Electric gives them.
- 01Check the motor and drive are compatible.
- 02Check the motor is connected during autotuning.
- 03If an output contactor is used, close it during autotuning.
- 04Check the motor is stopped during tuning.
Also in the manual
- Can be cleared by Auto Fault Reset (ATR), or with the Fault Reset Assign (RSF) input or control bit, after the cause is removed. Switching the drive off and on also clears it.
03 / Clearing it
How to clear TNF
- Remove the cause first. A resettable error can then be cleared by switching the drive off until the display goes out completely and back on, automatically by the Auto Fault Reset (ATR) function, through an input or control bit assigned to Fault reset (RST), or with the STOP/RESET key on the graphic display terminal when it is the active command channel.
- Some codes need a power reset (ANF, ASF, BLF, BRF, CRF1, EEF1, EEF2, FCF1, HDF, ILF, the INF codes, SAFF, SOF, SPF); ASF, BRF, SOF, SPF and TNF can also be cleared remotely with Fault Reset Assign (RSF).
- For an error that cannot be reset, Schneider's steps are: disconnect all power, including external control power; lock the disconnects open; wait 15 minutes for the DC bus capacitors to discharge; check the DC bus between PA/+ and PC/- is below 42 V DC; find and fix the cause; then restore power to confirm.
Clear it once. If TNF comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How motor identification faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check the motor is connected and the output contactor (if any) is closed during the run.
- 02Check the rating plate data entered in the drive and the motor connection (star or delta).
- 03Repeat the identification with the motor cold and uncoupled where possible.
05 / Repair
When TNF means a repair
Repeated failures on a correctly entered, healthy motor point at a winding fault or a drive measurement problem.
If TNF keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Schneider Electric drives, and they arrive knowing what to look for.
06 / Other drives
Motor identification: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F41 Motor data identification failure |
| Siemens SINAMICS G120 | A07980 Rotary measurement activated · A07981 No enabling for rotary measurement · A07991 Motor identification activated |
| Siemens SINAMICS V90 | F7995 Motor identification failure · A7971 Angular commutation offset determination activated · A7991 Motor data identification activated |
| Siemens MICROMASTER 440 | F0041 Failure, motor data identification · F0042 Fault/error when optimizing the speed controller |
| Allen-Bradley PowerFlex 525 | F080 Autotune Failure |
| ABB ACS355 | F0011 ID RUN FAIL · A2019 ID RUN · A2025 FIRST START |
| Delta VFD-E | AUE Auto tuning error |
| Delta C2000 | AUE Auto-tuning error · AUE1 Auto-tune error 1 · AUE2 Auto-tune error 2 · AUE3 Auto-tune error 3 · AUE4 Auto-tune error 4 |
| INVT Goodrive20 (GD20) | tE Motor autotuning fault · STo Maladjustment fault |
| Yaskawa V1000 | Er-01 Motor Data Error · Er-02 Minor Fault · Er-03 STOP Button Input · Er-04 Line-to-Line Resistance Error · Er-05 No-Load Current Error · Er-08 Rated Slip Error |
| Yaskawa A1000 | dv7 Initial Polarity Estimation Timeout · End1 Excessive V/f Setting · End2 Motor Iron-Core Saturation Coefficient · End3 Rated Current Setting Alarm · End4 Adjusted Slip Calculation Error · End5 Resistance Tuning Error |
| Yaskawa GA500 | dv7 Polarity Judge Timeout · End1 Excessive Rated Voltage Setting · End2 Iron Core Saturation Coefficient · End3 Rated Current Setting Alarm · End4 Adjusted Slip Calculation Error · End5 Resistance Tuning Error |
| Siemens MICROMASTER 420 | F0041 Failure, motor data identification · A0541 Motor data identification routine active |
| Siemens MICROMASTER 430 | F0041 Failure, motor data identification · A0541 Motor data identification routine active |
| INVT Goodrive200A (GD200A) | tE Motor autotuning fault |
| Danfoss VLT Micro Drive FC 51 | Alarm 51 AMT check Unom and Inom · Alarm 52 AMT low Inom · Alarm 53 AMT motor too big · Alarm 54 AMT motor too small · Alarm 55 AMT parameter out of range |
07 / More codes
Other Altivar ATV320 codes
Source
Schneider Electric, Altivar Machine ATV320 Programming Manual, 04/2025, NVE41295.06, Diagnostics and Troubleshooting.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Schneider Electric and is not its authorised service partner.