F0222 on the Siemens MICROMASTER 440 is the “PID feedback above maximum value” fault. On a fault the inverter switches off and shows the fault code; it will not run until the fault is reset.
A process value the drive controls (a PID feedback such as pressure or flow) went outside its set limits, or a pump protection function tripped.
- Code
- F0222
- Type
- Fault (stops the drive)
- Drive
- Siemens MICROMASTER 440
- Kind of fault
- Process limit
01 / Causes
What causes F0222
- The PID feedback rose above the maximum set in P2267.
02 / Checks
What to check for F0222
In the order Siemens gives them.
- 01Change the value of P2267.
- 02Adjust the feedback gain.
03 / Clearing it
How to clear F0222
- Reset a fault in one of three ways: switch the power off and on, press the Fn button on the BOP or AOP, or use digital input 3 (its default setting).
- Fault codes are stored in r0947 (F0003 is stored as 3), with the fault value in r0949, the time of the fault in r0948 and the number of stored faults in P0952.
- Alarm codes are stored in r2110 (A0503 is stored as 503).
Clear it once. If F0222 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How process limit faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check the process itself: a closed valve, an empty tank, a blocked line.
- 02Check the feedback transmitter and its wiring.
- 03Check the limit and gain settings in the drive.
05 / Repair
When F0222 means a repair
Usually a process or sensor problem rather than the drive.
If F0222 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.
06 / Other drives
Process limit: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F221 PID feedback below minimum value · F222 PID feedback above maximum value · F410 Cavitation protection failure · A930 Cavitation protection warn |
| Siemens SINAMICS G120 | F07426 Technology controller actual value limited · F07445 PID autotuning canceled · A07444 PID autotuning is activated |
| ABB ACS355 | A2018 PID SLEEP |
| Delta VFD-E | FbE PID feedback signal error |
| Yaskawa V1000 | FbH Excessive PID Feedback · FbL PID Feedback Loss |
| Yaskawa A1000 | FbH Excessive PID Feedback · FbL PID Feedback Loss |
| Yaskawa GA500 | CP1 Comparator 1 Limit Fault · CP2 Comparator 2 Limit Fault · FbH Excessive PID Feedback · FbL PID Feedback Loss |
| Siemens MICROMASTER 420 | F0221 PID feedback below the minimum value · F0222 PID feedback above maximum value |
| Siemens MICROMASTER 430 | F0221 PID feedback below the minimum value · F0222 PID feedback above maximum value |
07 / More codes
Other MICROMASTER 440 codes
Source
Siemens, MICROMASTER 440 Parameter List, Issue 01/06, 6SE6400-5BB00-0BP0, Section 5, Faults and Alarms.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007