V1000 FbH: Excessive PID Feedback

FbH on the Yaskawa V1000 is the “Excessive PID Feedback” fault. A fault interrupts the drive's output and the motor coasts to a stop (unless set to stop another way). The drive stays inoperable until the fault is reset, and a digital output set for fault (H2-oo = E) closes.

A process value the drive controls (a PID feedback such as pressure or flow) went outside its set limits, or a pump protection function tripped.

Code
FbH
Type
Fault (stops the drive)
Drive
Yaskawa V1000
Kind of fault
Process limit

01 / Causes

What causes FbH

  • The PID feedback stayed above the level in b5-36 for longer than b5-37. Detection is on when b5-12 is 2 or 5.
  • Wrong settings, wrong feedback wiring, or a faulty feedback sensor.

02 / Checks

What to check for FbH

In the order Yaskawa gives them.

  1. 01Check b5-36 and b5-37.
  2. 02Correct the PID feedback wiring.
  3. 03Check the sensor on the control side and replace it if damaged.

Also in the manual

  • The V1000 can also show this code as a minor fault: the ALM LED flashes instead of staying lit, and the motor keeps running.

03 / Clearing it

How to clear FbH

  • Fix the cause, then reset with the reset key on the digital operator, or by closing and opening terminal S4, which is the fault reset input by default.
  • If neither clears it, switch off the drive's main power and switch it back on once the operator display has gone out.
  • Some faults need a condition met before they reset: oL1 cannot be reset until monitor U4-16 is below 100.

Clear it once. If FbH comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How process limit faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check the process itself: a closed valve, an empty tank, a blocked line.
  2. 02Check the feedback transmitter and its wiring.
  3. 03Check the limit and gain settings in the drive.

05 / Repair

When FbH means a repair

Usually a process or sensor problem rather than the drive.

If FbH keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.

06 / Other drives

Process limit: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F221 PID feedback below minimum value · F222 PID feedback above maximum value · F410 Cavitation protection failure · A930 Cavitation protection warn
Siemens SINAMICS G120F07426 Technology controller actual value limited · F07445 PID autotuning canceled · A07444 PID autotuning is activated
Siemens MICROMASTER 440F0221 PID feedback below the minimum value · F0222 PID feedback above maximum value
ABB ACS355A2018 PID SLEEP
Delta VFD-EFbE PID feedback signal error
Yaskawa A1000FbH Excessive PID Feedback · FbL PID Feedback Loss
Yaskawa GA500CP1 Comparator 1 Limit Fault · CP2 Comparator 2 Limit Fault · FbH Excessive PID Feedback · FbL PID Feedback Loss
Siemens MICROMASTER 420F0221 PID feedback below the minimum value · F0222 PID feedback above maximum value
Siemens MICROMASTER 430F0221 PID feedback below the minimum value · F0222 PID feedback above maximum value

07 / More codes

Other V1000 codes

Source

Yaskawa, YASKAWA AC Drive V1000 Technical Manual, 18F, SIEP C710606 18, 6.4 Fault Detection.