FbL on the Yaskawa V1000 is the “PID Feedback Loss” fault. A fault interrupts the drive's output and the motor coasts to a stop (unless set to stop another way). The drive stays inoperable until the fault is reset, and a digital output set for fault (H2-oo = E) closes.
A process value the drive controls (a PID feedback such as pressure or flow) went outside its set limits, or a pump protection function tripped.
- Code
- FbL
- Type
- Fault (stops the drive)
- Drive
- Yaskawa V1000
- Kind of fault
- Process limit
01 / Causes
What causes FbL
- PID feedback loss detection is set to fault (b5-12 = 2) and the feedback stayed below b5-13 for the time in b5-14.
- Wrong settings, wrong feedback wiring, or a faulty feedback sensor.
02 / Checks
What to check for FbL
In the order Yaskawa gives them.
- 01Check b5-13 and b5-14.
- 02Correct the PID feedback wiring.
- 03Check the sensor on the controller side and replace it if damaged.
Also in the manual
- The V1000 can also show this code as a minor fault: the ALM LED flashes instead of staying lit, and the motor keeps running.
03 / Clearing it
How to clear FbL
- Fix the cause, then reset with the reset key on the digital operator, or by closing and opening terminal S4, which is the fault reset input by default.
- If neither clears it, switch off the drive's main power and switch it back on once the operator display has gone out.
- Some faults need a condition met before they reset: oL1 cannot be reset until monitor U4-16 is below 100.
Clear it once. If FbL comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How process limit faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check the process itself: a closed valve, an empty tank, a blocked line.
- 02Check the feedback transmitter and its wiring.
- 03Check the limit and gain settings in the drive.
05 / Repair
When FbL means a repair
Usually a process or sensor problem rather than the drive.
If FbL keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.
06 / Other drives
Process limit: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F221 PID feedback below minimum value · F222 PID feedback above maximum value · F410 Cavitation protection failure · A930 Cavitation protection warn |
| Siemens SINAMICS G120 | F07426 Technology controller actual value limited · F07445 PID autotuning canceled · A07444 PID autotuning is activated |
| Siemens MICROMASTER 440 | F0221 PID feedback below the minimum value · F0222 PID feedback above maximum value |
| ABB ACS355 | A2018 PID SLEEP |
| Delta VFD-E | FbE PID feedback signal error |
| Yaskawa A1000 | FbH Excessive PID Feedback · FbL PID Feedback Loss |
| Yaskawa GA500 | CP1 Comparator 1 Limit Fault · CP2 Comparator 2 Limit Fault · FbH Excessive PID Feedback · FbL PID Feedback Loss |
| Siemens MICROMASTER 420 | F0221 PID feedback below the minimum value · F0222 PID feedback above maximum value |
| Siemens MICROMASTER 430 | F0221 PID feedback below the minimum value · F0222 PID feedback above maximum value |
07 / More codes
Other V1000 codes
Source
Yaskawa, YASKAWA AC Drive V1000 Technical Manual, 18F, SIEP C710606 18, 6.4 Fault Detection.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007