MachineryFix

Yaskawa AC drive (VFD) · fault code

GA500 FbH: Excessive PID Feedback

FbH on the Yaskawa GA500 is the “Excessive PID Feedback” fault. A fault shuts off the drive's output and the motor coasts to a stop (some faults let you choose the stopping method). ALM/ERR stays lit, a terminal set to H2-01 to H2-03 = E activates, and the drive will not run until the fault is reset.

A process value the drive controls (a PID feedback such as pressure or flow) went outside its set limits, or a pump protection function tripped.

Code
FbH
Type
Fault (stops the drive)
Drive
Yaskawa GA500
Kind of fault
Process limit

01 / Causes

What causes FbH

  • The FbH detection level is set wrongly, the PID feedback wiring is faulty, the feedback sensor is not working, or the drive's feedback input circuit has failed.

02 / Checks

What to check for FbH

In the order Yaskawa gives them.

  1. 01Adjust b5-36 (level) and b5-37 (time).
  2. 02Correct the PID feedback wiring.
  3. 03Examine the sensor on the controlled device.
  4. 04Replace the control board or the drive (contact Yaskawa about replacing the control board).

Also in the manual

  • Detected when PID feedback stays above b5-36 for longer than b5-37. b5-12 sets the stopping method.
  • The GA500 can also show this code as a minor fault or alarm: ALM/ERR flashes instead of staying lit, and the drive keeps running unless set to stop.

03 / Clearing it

How to clear FbH

  • Remove the cause, then reset in one of three ways: the reset key on the keypad while the code is shown, a multi-function input set to H1-xx = 14 (terminal S4 by default), or switching off the main circuit power and switching it back on once the keypad display has gone out.
  • A fault will not reset while a run command is active from the terminals or a communication option; the keypad shows CrST until the run command is removed.
  • oL1 resets only once monitor U4-16 (Motor oL1 Level) is below 100.

Clear it once. If FbH comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How process limit faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check the process itself: a closed valve, an empty tank, a blocked line.
  2. 02Check the feedback transmitter and its wiring.
  3. 03Check the limit and gain settings in the drive.

05 / Repair

When FbH means a repair

Usually a process or sensor problem rather than the drive.

If FbH keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.

06 / Other drives

Process limit: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F221 PID feedback below minimum value · F222 PID feedback above maximum value · F410 Cavitation protection failure · A930 Cavitation protection warn
Siemens SINAMICS G120F07426 Technology controller actual value limited · F07445 PID autotuning canceled · A07444 PID autotuning is activated
Siemens MICROMASTER 440F0221 PID feedback below the minimum value · F0222 PID feedback above maximum value
ABB ACS355A2018 PID SLEEP
Delta VFD-EFbE PID feedback signal error
Yaskawa V1000FbH Excessive PID Feedback · FbL PID Feedback Loss
Yaskawa A1000FbH Excessive PID Feedback · FbL PID Feedback Loss
Siemens MICROMASTER 420F0221 PID feedback below the minimum value · F0222 PID feedback above maximum value
Siemens MICROMASTER 430F0221 PID feedback below the minimum value · F0222 PID feedback above maximum value

07 / More codes

Other GA500 codes

Source

Yaskawa, GA500 Drive Technical Reference, C, SIEP C710617 52, 7 Troubleshooting (7.4 to 7.7, 7.9).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007