FbL on the Yaskawa A1000 is the “PID Feedback Loss” fault. A fault is detected for drive protection: it stops the drive and toggles the fault output on terminals MA-MB-MC. Remove the cause and clear the fault before running again.
A process value the drive controls (a PID feedback such as pressure or flow) went outside its set limits, or a pump protection function tripped.
- Code
- FbL
- Type
- Fault (stops the drive)
- Drive
- Yaskawa A1000
- Kind of fault
- Process limit
01 / Causes
What causes FbL
- PID feedback loss detection is set to fault (b5-12 = 2 or 5) and the feedback stayed below b5-13 for longer than b5-14: wrong settings, wrong wiring or a faulty sensor.
02 / Checks
What to check for FbL
In the order Yaskawa gives them.
- 01Check b5-13 and b5-14.
- 02Correct the PID feedback wiring.
- 03Check the sensor and replace it if damaged.
Also in the manual
- The A1000 can also raise this code as an alarm: the ALM light blinks, the code flashes, and the drive does not necessarily stop.
03 / Clearing it
How to clear FbL
- Remove the cause, then clear the fault manually before running again: the reset key on the digital operator, a multi-function input set to fault reset, or cycling the power.
- Some faults need a condition met first: oL1 cannot be reset until monitor U4-16 is below 100%. SC will not accept a reset at all, to protect the drive's internal circuits.
Clear it once. If FbL comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How process limit faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check the process itself: a closed valve, an empty tank, a blocked line.
- 02Check the feedback transmitter and its wiring.
- 03Check the limit and gain settings in the drive.
05 / Repair
When FbL means a repair
Usually a process or sensor problem rather than the drive.
If FbL keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.
06 / Other drives
Process limit: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F221 PID feedback below minimum value · F222 PID feedback above maximum value · F410 Cavitation protection failure · A930 Cavitation protection warn |
| Siemens SINAMICS G120 | F07426 Technology controller actual value limited · F07445 PID autotuning canceled · A07444 PID autotuning is activated |
| Siemens MICROMASTER 440 | F0221 PID feedback below the minimum value · F0222 PID feedback above maximum value |
| ABB ACS355 | A2018 PID SLEEP |
| Delta VFD-E | FbE PID feedback signal error |
| Yaskawa V1000 | FbH Excessive PID Feedback · FbL PID Feedback Loss |
| Yaskawa GA500 | CP1 Comparator 1 Limit Fault · CP2 Comparator 2 Limit Fault · FbH Excessive PID Feedback · FbL PID Feedback Loss |
| Siemens MICROMASTER 420 | F0221 PID feedback below the minimum value · F0222 PID feedback above maximum value |
| Siemens MICROMASTER 430 | F0221 PID feedback below the minimum value · F0222 PID feedback above maximum value |
07 / More codes
Other A1000 codes
Source
Yaskawa, YASKAWA AC Drive A1000 Quick Start Guide, 41G, TOEP C710616 41, 5.2 to 5.5: Fault Detection, Alarm Detection, Operator Programming Errors, Auto-Tuning Fault Detection.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007