MachineryFix

Siemens AC drive (VFD) · fault code

MICROMASTER 420 F0080: ADC input signal lost

F0080 on the Siemens MICROMASTER 420 is the “ADC input signal lost” fault. On a fault the inverter switches off and shows the fault code (Siemens' reaction STOP II); it will not run until the fault is reset.

An analog input (usually a 4-20 mA speed reference or feedback) dropped out of its expected range, most often from a broken wire or a failed transmitter.

Code
F0080
Type
Fault (stops the drive)
Drive
Siemens MICROMASTER 420
Kind of fault
Analog signal loss

01 / Causes

What causes F0080

  • A broken wire.
  • The signal is outside its limits.

02 / Checks

What to check for F0080

In the order Siemens gives them.

The manual gives no specific remedy for F0080. Work through the general method for analog signal loss faults below.

03 / Clearing it

How to clear F0080

  • Reset a fault in one of three ways: switch the power off and on, press the Fn button on the BOP or AOP, or use digital input 3 (its default setting).
  • Fault codes are stored in r0947 (F0003 is stored as 3), with the fault value in r0949 (0 when the fault has none), the time of the fault in r0948 and the number of stored faults in P0952.
  • Alarm codes are stored in r2110 (A0503 is stored as 503).

Clear it once. If F0080 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How analog signal loss faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Measure the signal at the drive terminals while the system runs.
  2. 02Check the wiring back to the source for breaks and loose terminals.
  3. 03Check the transmitter or the PLC's analog output that supplies the signal.

05 / Repair

When F0080 means a repair

If the signal is correct at the terminals, the drive's analog input may have failed.

If F0080 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.

06 / Other drives

Analog signal loss: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F80 Signal lost on analog input
Siemens SINAMICS G120F03505 Analog input, wire break
Siemens MICROMASTER 440F0080 ADC input signal lost
Allen-Bradley PowerFlex 525F029 Analog In Loss
ABB ACS355F0007 AI1 LOSS · F0008 AI2 LOSS · A2006 AI1 LOSS · A2007 AI2 LOSS
Delta VFD-EAErr ACI signal error
Delta C2000AFE PID loss ACI · ACE ACI loss
Schneider Electric Altivar ATV320LFF3 AI3 4-20mA loss error
INVT Goodrive20 (GD20)PIDE PID feedback offline fault
Siemens MICROMASTER 430F0080 ADC input signal lost
INVT Goodrive200A (GD200A)PIDE PID feedback offline fault
Danfoss VLT Micro Drive FC 51Alarm 2 Live zero error

07 / More codes

Other MICROMASTER 420 codes

Source

Siemens, MICROMASTER 420 Parameter List, Issue 10/06, 6SE6400-5BA00-0BP0, Section 5, Faults and Alarms.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

F0080 won't clear? Get a technician who knows the MICROMASTER 420.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.