A0511 on the Siemens MICROMASTER 420 is the “Motor overtemperature I2t” alarm. An alarm is a warning shown while the inverter keeps running; some alarms reduce the pulse or output frequency to protect the inverter.
The drive's motor protection, either a thermal model or a sensor in the winding, says the motor is too hot. Running a self-cooled motor at low speed is a common cause: its fan slows with it.
- Code
- A0511
- Type
- Alarm (warning)
- Drive
- Siemens MICROMASTER 420
- Kind of fault
- Motor overload or overtemperature
01 / Causes
What causes A0511
- The motor is overloaded.
- The load duty cycle is exceeded.
02 / Checks
What to check for A0511
In the order Siemens gives them.
- 01Check the motor I2t time constant P0611 is suitable.
- 02Check the motor I2t overload alarm P0614 is set to a suitable value.
03 / Clearing it
How to clear A0511
An alarm is a warning shown while the inverter keeps running; some alarms reduce the pulse or output frequency to protect the inverter.
If A0511 stays on, work through the checks above: an alarm that is ignored often becomes a fault that stops the machine.
04 / On site
How motor overload or overtemperature faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Compare running current with the motor's rating plate current.
- 02Check the motor overload settings in the drive against the rating plate.
- 03Feel and measure the motor frame temperature, and check that its cooling fan and fins are clear.
- 04If the motor runs for long periods at low speed, ask whether it needs a separately powered cooling fan.
05 / Repair
When A0511 means a repair
A motor that is genuinely overheating at normal current may have a winding or bearing problem; test the windings and listen to the bearings before resetting again.
If A0511 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.
06 / Other drives
Motor overload or overtemperature: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F11 Motor overtemperature · A511 Motor overtemperature I2t |
| Siemens SINAMICS G120 | F07011 Motor overtemperature · A07012 I2t motor model overtemperature · A07910 Motor overtemperature |
| Siemens SINAMICS V90 | F7011 Motor overtemperature · A7012 Motor temperature model 1/3 overtemperature |
| Siemens MICROMASTER 440 | F0011 Motor overtemperature · A0511 Motor overtemperature |
| Allen-Bradley PowerFlex 525 | F007 Motor Overload |
| ABB ACS355 | F0009 MOT OVERTEMP · A2010 MOTOR TEMP |
| Delta VFD-E | oL1 Overload 1 · oL2 Overload 2 · PtC1 Motor PTC overheat protection |
| Delta C2000 | EoL1 Electronic thermal relay 1 protection · EoL2 Electronic thermal relay 2 protection · oH3 Motor overheating |
| Delta ASDA-B2 | AL006 Overload · AL035 Encoder temperature exceeds the protective range · AL067 Encoder temperature warning · AL023 Early warning for overload |
| Hitachi WJ200 | E05 Overload protection · E35 Thermistor |
| Schneider Electric Altivar ATV320 | OLF Motor overload error · OTFL DI6=PTC overheat error |
| INVT Goodrive20 (GD20) | OL1 Motor overload |
| Yaskawa V1000 | oH3 Motor Overheat Alarm (PTC Input) · oH4 Motor Overheat Fault (PTC Input) · oL1 Motor Overload |
| Yaskawa A1000 | oH3 Motor Overheat Alarm (PTC Input) · oH4 Motor Overheat Fault (PTC Input) · oH5 Motor Overheat (NTC Input) · oL1 Motor Overload |
| Yaskawa GA500 | oH3 Motor Overheat (PTC Input) · oH4 Motor Overheat Fault (PTC Input) · oL1 Motor Overload |
| Siemens MICROMASTER 430 | F0011 Motor overtemperature · A0511 Motor overtemperature |
| Siemens SINAMICS G110 | F0011 Motor over temperature I2t · A0511 Motor over temperature I2t |
| INVT Goodrive200A (GD200A) | OL1 Motor overload |
| Mitsubishi Electric FR-D700 | E.THM Motor overload trip (electronic thermal O/L relay function) · TH Electronic thermal relay function pre-alarm |
| Danfoss VLT Micro Drive FC 51 | Alarm 10 Motor ETR over temperature |
07 / More codes
Other MICROMASTER 420 codes
Source
Siemens, MICROMASTER 420 Parameter List, Issue 10/06, 6SE6400-5BA00-0BP0, Section 5, Faults and Alarms.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007