MachineryFix

Siemens AC drive (VFD) · fault code

MICROMASTER 420 F0051: Parameter EEPROM fault

F0051 on the Siemens MICROMASTER 420 is the “Parameter EEPROM fault” fault. On a fault the inverter switches off and shows the fault code (Siemens' reaction STOP II); it will not run until the fault is reset.

The drive could not read or write its stored parameters, or found them invalid. The drive may start with wrong settings, or refuse to start.

Code
F0051
Type
Fault (stops the drive)
Drive
Siemens MICROMASTER 420
Kind of fault
Parameter memory

01 / Causes

What causes F0051

  • A read or write while saving parameters to the EEPROM failed.

02 / Checks

What to check for F0051

In the order Siemens gives them.

  1. 01Reset to factory settings and set the parameters again.
  2. 02If that does not clear it, replace the drive.

03 / Clearing it

How to clear F0051

  • Reset a fault in one of three ways: switch the power off and on, press the Fn button on the BOP or AOP, or use digital input 3 (its default setting).
  • Fault codes are stored in r0947 (F0003 is stored as 3), with the fault value in r0949 (0 when the fault has none), the time of the fault in r0948 and the number of stored faults in P0952.
  • Alarm codes are stored in r2110 (A0503 is stored as 503).

Clear it once. If F0051 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How parameter memory faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Power-cycle the drive and see whether the fault clears.
  2. 02If it returns, restore the parameters from a backup, or reset to factory settings and set the drive up again.
  3. 03Keep a parameter backup of every drive, so this never means guessing the settings.

05 / Repair

When F0051 means a repair

A memory fault that survives a factory reset needs the control board repaired or replaced.

If F0051 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.

06 / Other drives

Parameter memory: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F51 Parameter EEPROM fault · F61 SD card parameter cloning failed · F62 Parameter cloning contents invalid · F63 Parameter cloning contents incompatible · F64 Inverter attempted to do an automatic clone during startup · F395 Acceptance test/confirmation pending
Siemens SINAMICS G120F01040 Parameters must be saved · F01044 Error loading data from memory card · F01105 CU: Insufficient memory · F13100 Know-how protection: Copy protection error · F13101 Know-how protection: Copy protection cannot be activated · A01101 Memory card not available
Siemens SINAMICS V90A1019 Writing to the removable data medium unsuccessful · A1032 All parameters must be saved · A1045 Configuring data invalid · A52900 Failure during data copying
Siemens MICROMASTER 440F0051 Parameter EEPROM fault
Allen-Bradley PowerFlex 525F048 Params Defaulted · F100 Parameter Chksum · F101 External Storage
ABB ACS355A5010 Corrupted panel parameter backup file · A5018 Parameter default value is not found · A5025 Software is being uploaded or downloaded · A5029 Memory is not ready · A5040 Parameter download error: the selected set is not in the backup file · A5041 Parameter backup file does not fit into memory
Delta VFD-EcF1.0 Power board CPU write failure · cF1.1 Control board CPU write failure · cF2.0 Power board CPU read failure · cF2.1 Control board CPU read failure
Delta C2000cF1 EEPROM write error · cF2 EEPROM read error
Delta ASDA-B2AL017 Abnormal EEPROM · AL099 DSP firmware upgrade
Hitachi WJ200E08 EEPROM error
Schneider Electric Altivar ATV320EEF1 EEprom control error · EEF2 EEprom power error
INVT Goodrive20 (GD20)EEP EEPROM operation fault
Yaskawa V1000CPF06 EEPROM Data Error · Err EEPROM Write Error
Yaskawa A1000CPF06 EEPROM Memory Data Error · dWF1 EEPROM Memory DriveWorksEZ Data Error · Err EEPROM Write Error
Yaskawa GA500CPF06 Control Circuit Error (EEPROM memory Data Error) · dWF1 EEPROM Memory DWEZ Data Error · Err EEPROM Write Error · LoG Log Com Error
Siemens MICROMASTER 430F0051 Parameter EEPROM fault · F0053 I/O EEPROM fault
Siemens SINAMICS G110F0051 Parameter EEPROM fault · F0055 BOP-EEPROM fault
INVT Goodrive200A (GD200A)EEP EEPROM operation fault
Mitsubishi Electric FR-D700E.PE Parameter storage device fault (control circuit board)
Danfoss VLT Micro Drive FC 51Error 86 Copy fail · Error 87 LCP data invalid · Error 88 LCP data not compatible

07 / More codes

Other MICROMASTER 420 codes

Source

Siemens, MICROMASTER 420 Parameter List, Issue 10/06, 6SE6400-5BA00-0BP0, Section 5, Faults and Alarms.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

F0051 won't clear? Get a technician who knows the MICROMASTER 420.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.