F0005 on the Siemens MICROMASTER 420 is the “Inverter I2t” fault. On a fault the inverter switches off and shows the fault code (Siemens' reaction STOP II); it will not run until the fault is reset.
The drive's own overload model says it has carried more current, for longer, than its rating allows. The drive is undersized for the duty, or the load has grown.
- Code
- F0005
- Type
- Fault (stops the drive)
- Drive
- Siemens MICROMASTER 420
- Kind of fault
- Drive overload
01 / Causes
What causes F0005
- The inverter is overloaded.
- The load duty cycle is too high.
- The motor's rated power (P0307) is greater than the inverter's (r0206).
- The 100% overload level has been reached (see utilisation r0036).
02 / Checks
What to check for F0005
In the order Siemens gives them.
- 01Check the load duty cycle is within the permitted limits.
- 02Use a motor with a lower rating if P0307 is greater than the inverter power r0206.
03 / Clearing it
How to clear F0005
- Reset a fault in one of three ways: switch the power off and on, press the Fn button on the BOP or AOP, or use digital input 3 (its default setting).
- Fault codes are stored in r0947 (F0003 is stored as 3), with the fault value in r0949 (0 when the fault has none), the time of the fault in r0948 and the number of stored faults in P0952.
- Alarm codes are stored in r2110 (A0503 is stored as 503).
Clear it once. If F0005 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How drive overload faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Record the running current and compare it with the drive's rated current.
- 02Look for a change in the load: a dragging bearing, a tighter belt, a heavier product, a blocked impeller.
- 03Check acceleration time and boost settings; long periods at high torque add up quickly.
05 / Repair
When F0005 means a repair
If the current is well within the rating and the code keeps returning, the drive's current measurement should be checked on the bench.
If F0005 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.
06 / Other drives
Drive overload: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F5 Inverter I2t · A505 Inverter I2t |
| Siemens SINAMICS G120 | F30005 I2t inverter overload · A07805 Drive: Power unit overload I2t |
| Siemens SINAMICS V90 | F30005 Power unit: Overload I2t |
| Siemens MICROMASTER 440 | F0005 Inverter I2T · A0505 Inverter I2T |
| Allen-Bradley PowerFlex 525 | F064 Drive Overload |
| Delta VFD-E | oL Overload |
| Delta C2000 | oL Over load · oL3 Overload protection at low frequency |
| Hitachi WJ200 | E38 Low-speed overload protection |
| INVT Goodrive20 (GD20) | OL2 VFD overload |
| Yaskawa V1000 | oL2 Drive Overload |
| Yaskawa A1000 | oL2 Drive Overload |
| Yaskawa GA500 | oL2 Drive Overload |
| Siemens MICROMASTER 430 | F0005 Inverter I2t · A0505 Inverter I2t · A0506 Inverter load duty cycle |
| Siemens SINAMICS G110 | F0005 Inverter I2t · A0505 Inverter I2t |
| INVT Goodrive200A (GD200A) | OL2 VFD overload |
| Mitsubishi Electric FR-D700 | E.THT Inverter overload trip (electronic thermal O/L relay function) |
| Danfoss VLT Micro Drive FC 51 | Alarm 9 Inverter overloaded |
07 / More codes
Other MICROMASTER 420 codes
Source
Siemens, MICROMASTER 420 Parameter List, Issue 10/06, 6SE6400-5BA00-0BP0, Section 5, Faults and Alarms.