F0003 on the Siemens MICROMASTER 420 is the “Undervoltage” fault. On a fault the inverter switches off and shows the fault code (Siemens' reaction STOP II); it will not run until the fault is reset.
The DC bus voltage fell below the level the drive needs to run. Most often the supply dipped or one phase was lost, but a failing pre-charge circuit or tired DC bus capacitors give the same code.
- Code
- F0003
- Type
- Fault (stops the drive)
- Drive
- Siemens MICROMASTER 420
- Kind of fault
- DC bus undervoltage
01 / Causes
What causes F0003
- The supply voltage failed.
- Shock loading outside the permitted limits.
02 / Checks
What to check for F0003
In the order Siemens gives them.
- 01Check the supply voltage is within the permitted range.
- 02Check the supply is stable, without sporadic failures or voltage dips (brown-outs).
03 / Clearing it
How to clear F0003
- Reset a fault in one of three ways: switch the power off and on, press the Fn button on the BOP or AOP, or use digital input 3 (its default setting).
- Fault codes are stored in r0947 (F0003 is stored as 3), with the fault value in r0949 (0 when the fault has none), the time of the fault in r0948 and the number of stored faults in P0952.
- Alarm codes are stored in r2110 (A0503 is stored as 503).
Clear it once. If F0003 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How dc bus undervoltage faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check whether the trip lines up with other plant loads starting, generator changeovers or known supply dips.
- 02Measure all three supply phases at the drive terminals, and check input fuses and contactor contacts.
- 03Look for loose or heat-discoloured supply terminals.
- 04If the supply is steady, record the DC bus voltage reading from the drive's display while running.
05 / Repair
When F0003 means a repair
A drive that shows undervoltage on a healthy, steady supply usually has a failed pre-charge relay or resistor, or aged DC bus capacitors. Both are repaired on the bench.
If F0003 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.
06 / Other drives
DC bus undervoltage: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F3 Undervoltage · A503 Undervoltage limit · A912 Vdc_min controller active |
| Siemens SINAMICS G120 | F30003 DC-link voltage undervoltage · F30027 Time monitoring for DC link pre-charging |
| Siemens SINAMICS V90 | F7403 Lower DC link voltage threshold reached · F30003 DC link voltage, undervoltage · F30027 Precharging DC link time monitoring · A30016 Load supply switched off |
| Siemens MICROMASTER 440 | F0003 Undervoltage · A0503 Undervoltage limit value · A0912 Vdc-min controller active |
| Allen-Bradley PowerFlex 525 | F003 Power Loss · F004 UnderVoltage |
| ABB ACS355 | F0006 DC UNDERVOLT · A2003 UNDERVOLTAGE · A5031 Drive is not ready for operation, for example because of low DC voltage |
| Delta VFD-E | Lv Low voltage · dEb Deceleration energy backup error |
| Delta C2000 | LvA Low-voltage during acceleration · Lvd Low-voltage during deceleration · Lvn Low-voltage at constant speed · LvS Low-voltage at stop · dEb Deceleration energy backup error |
| Delta ASDA-B2 | AL003 Under voltage |
| Hitachi WJ200 | E09 Under-voltage error |
| Schneider Electric Altivar ATV320 | USF Supply mains undervoltage error |
| INVT Goodrive20 (GD20) | UV Bus undervoltage · PoFF System power off |
| Yaskawa V1000 | Uv1 DC Bus Undervoltage · Uv2 Control Power Supply Voltage Fault · Uv Undervoltage |
| Yaskawa A1000 | Uv1 DC Bus Undervoltage · Uv2 Control Power Supply Voltage Fault · Uv Undervoltage |
| Yaskawa GA500 | Uv1 DC Bus Undervoltage · Uv2 Control Power Undervoltage · EP24v External Power 24V Supply · L24v Loss of External Power 24 Supply · Uv DC Bus Undervoltage |
| Siemens MICROMASTER 430 | F0003 Undervoltage · A0503 Undervoltage limit value |
| Siemens SINAMICS G110 | F0003 Undervoltage · A0503 Undervoltage limit |
| INVT Goodrive200A (GD200A) | UV Bus undervoltage · PoFF System power failure |
| Mitsubishi Electric FR-D700 | UV Undervoltage |
| Danfoss VLT Micro Drive FC 51 | Alarm 8 DC under voltage |
07 / More codes
Other MICROMASTER 420 codes
Source
Siemens, MICROMASTER 420 Parameter List, Issue 10/06, 6SE6400-5BA00-0BP0, Section 5, Faults and Alarms.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.