F0035 on the Siemens MICROMASTER 440 is the “Restart after n” fault. On a fault the inverter switches off and shows the fault code; it will not run until the fault is reset.
The drive tried to restart itself the number of times it is allowed to and gave up. The original fault is still there, and it is the one to find.
- Code
- F0035
- Type
- Fault (stops the drive)
- Drive
- Siemens MICROMASTER 440
- Kind of fault
- Automatic restart limit
01 / Causes
What causes F0035
- The automatic restart has failed after the number of attempts set in P1211.
02 / Checks
What to check for F0035
In the order Siemens gives them.
- 01Reset the fault memory, or switch power on, or stop.
03 / Clearing it
How to clear F0035
- Reset a fault in one of three ways: switch the power off and on, press the Fn button on the BOP or AOP, or use digital input 3 (its default setting).
- Fault codes are stored in r0947 (F0003 is stored as 3), with the fault value in r0949, the time of the fault in r0948 and the number of stored faults in P0952.
- Alarm codes are stored in r2110 (A0503 is stored as 503).
Clear it once. If F0035 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How automatic restart limit faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Read the fault history to find the fault that triggered the restarts.
- 02Fix that fault before clearing this one.
05 / Repair
When F0035 means a repair
This code is never the root cause on its own.
If F0035 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.
06 / Other drives
Automatic restart limit: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F35 Maximum number of auto restart attempts exceeded |
| Siemens SINAMICS G120 | F07320 Automatic restart aborted · A07321 Automatic restart active |
| Allen-Bradley PowerFlex 525 | F033 Auto Rstrt Tries |
| ABB ACS355 | A2013 AUTORESET |
| Yaskawa V1000 | SEr Too Many Speed Search Restarts |
| Yaskawa A1000 | SEr Too Many Speed Search Restarts |
| Yaskawa GA500 | SEr Speed Search Retries Exceeded |
| Siemens MICROMASTER 420 | F0035 Restart after n · A0571 Auto restart after fault present |
| Siemens MICROMASTER 430 | F0035 Restart after n · A0571 Auto restart after fault present |
| Mitsubishi Electric FR-D700 | E.RET Retry count excess |