F0022 on the Siemens MICROMASTER 440 is the “Hardware monitoring active” fault. On a fault the inverter switches off and shows the fault code; it will not run until the fault is reset.
The drive measured output current above its trip limit and switched its transistors off, usually within microseconds, to protect itself. The current came from somewhere: a short or earth fault in the cable or motor, a load that needed more torque than the ramp allowed, or motor data that does not match the motor.
- Code
- F0022
- Type
- Fault (stops the drive)
- Drive
- Siemens MICROMASTER 440
- Kind of fault
- Overcurrent
01 / Causes
What causes F0022
- A DC link overcurrent, meaning an IGBT short circuit.
- A short circuit in the braking chopper.
- An earth fault.
- The I/O module is not inserted correctly.
02 / Checks
What to check for F0022
In the order Siemens gives them.
- 01First find out whether the fault is permanent (the inverter cannot start without it) or sporadic.
- 02If permanent: check the I/O module is inserted correctly, then disconnect the motor cable to see whether the earth fault or short is outside the inverter.
- 03If the fault still occurs with all external cables except the supply disconnected, Siemens says the drive is very probably defective and must be repaired.
- 04If sporadic: treat it as overcurrent. Look for sudden load changes or mechanical obstructions, very short acceleration times, poorly optimised sensorless vector control, or a braking resistor with too low a resistance.
Also in the manual
- Which of these causes can occur depends on the frame size: all four on sizes A to C; the IGBT, chopper and I/O module causes on D and E; the IGBT and chopper causes on F.
- The causes share one signal in the power module, so the inverter cannot say which one occurred.
- On FX and GX frames, r0949 = 12, 13 or 14 identifies a UCE fault, and r0949 = 21 an I2C bus error (power down and up again).
03 / Clearing it
How to clear F0022
- Reset a fault in one of three ways: switch the power off and on, press the Fn button on the BOP or AOP, or use digital input 3 (its default setting).
- Fault codes are stored in r0947 (F0003 is stored as 3), with the fault value in r0949, the time of the fault in r0948 and the number of stored faults in P0952.
- Alarm codes are stored in r2110 (A0503 is stored as 503).
Clear it once. If F0022 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How overcurrent faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Note when it trips: at start, during acceleration, at steady speed or while stopping. A trip at the instant of start points at the cable or motor; a trip during acceleration points at the ramp or the load.
- 02With the supply isolated and the DC bus discharged, disconnect the motor cable at the drive and insulation-test the cable and motor windings to earth and between phases.
- 03Measure winding resistance phase to phase. The three readings should match closely; an unbalanced reading means a winding fault.
- 04Turn the load by hand where it is safe to do so, to rule out a seized bearing, jammed conveyor or dragging brake.
- 05Compare the motor rating plate with the motor parameters in the drive, then run the drive with the motor disconnected if the manual allows it. A trip with no motor connected points at the drive's output stage.
05 / Repair
When F0022 means a repair
If the drive trips on overcurrent with the motor disconnected, or the trip comes back the moment the drive is enabled with a healthy motor and cable, the output stage (IGBT module or its gate drive) has usually failed. That is a bench repair, not a setting.
If F0022 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.
06 / Other drives
Overcurrent: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F1 Overcurrent · A501 Current limit |
| Siemens SINAMICS G120 | F07801 Motor overcurrent · F30001 Overcurrent · A07409 V/f control, current limiting controller active |
| Siemens SINAMICS V90 | F7801 Motor overcurrent · F30001 Power unit: Overcurrent · A30031 Hardware current limiting in phase U |
| Allen-Bradley PowerFlex 525 | F012 HW OverCurrent · F063 SW OverCurrent |
| ABB ACS355 | F0001 OVERCURRENT · A2001 OVERCURRENT |
| Delta VFD-E | oc Over-current · ocA Over-current during acceleration · ocd Over-current during deceleration · ocn Over-current during constant speed |
| Delta C2000 | ocA Over-current during acceleration · ocd Over-current during deceleration · ocn Over-current during steady operation · ocS Over-current at stop |
| Delta ASDA-B2 | AL001 Over current |
| Hitachi WJ200 | E01 Over-current event while at constant speed · E02 Over-current event during deceleration · E03 Over-current event during acceleration · E04 Over-current event during other conditions |
| Schneider Electric Altivar ATV320 | OCF Overcurrent error |
| INVT Goodrive20 (GD20) | OC1 Overcurrent during acceleration · OC2 Overcurrent during deceleration · OC3 Overcurrent during constant speed running |
| Yaskawa V1000 | oC Overcurrent · HCA Current Alarm |
| Yaskawa A1000 | oC Overcurrent · HCA Current Alarm |
| Yaskawa GA500 | oC Overcurrent · oC2 Overcurrent2 · HCA High Current Alarm |
| Siemens MICROMASTER 420 | F0001 Overcurrent · A0501 Current limit value |
| Siemens MICROMASTER 430 | F0001 Overcurrent · A0501 Current limit value |
| Siemens SINAMICS G110 | F0001 Overcurrent · A0501 Current limit |
| INVT Goodrive200A (GD200A) | OC1 Overcurrent during acceleration · OC2 Overcurrent during deceleration · OC3 Overcurrent during constant speed running |
| Mitsubishi Electric FR-D700 | E.OC1 Overcurrent trip during acceleration · E.OC2 Overcurrent trip during constant speed · E.OC3 Overcurrent trip during deceleration or stop · OL Stall prevention (overcurrent) |
| Danfoss VLT Micro Drive FC 51 | Alarm 13 Over current · Warning 59 Current limit |
07 / More codes
Other MICROMASTER 440 codes
Source
Siemens, MICROMASTER 440 Parameter List, Issue 01/06, 6SE6400-5BB00-0BP0, Section 5, Faults and Alarms.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007