F07320 on the Siemens SINAMICS G120 is the “Automatic restart aborted” fault. A fault generally switches the motor off, and it must be acknowledged before the inverter runs again.
The drive tried to restart itself the number of times it is allowed to and gave up. The original fault is still there, and it is the one to find.
- Code
- F07320
- Type
- Fault (stops the drive)
- Drive
- Siemens SINAMICS G120, CU240B-2, CU240E-2
- Kind of fault
- Automatic restart limit
01 / Causes
What causes F07320
Siemens's table names this fault and lists what to do, but gives no separate cause. The checks below are the ones it lists; the section on tracing automatic restart limit faults explains where it usually comes from.
02 / Checks
What to check for F07320
In the order Siemens gives them.
- 01Increase the number of restart attempts (p1211); the current number of attempts is in r1214.
- 02Increase the wait time (p1212) and/or the monitoring time (p1213).
- 03Connect an ON command (p0840).
- 04Increase the power unit's monitoring time, or switch it off (p0857).
- 05Reduce the wait time for resetting the fault counter (p1213[1]), so fewer faults are counted in the interval.
03 / Clearing it
How to clear F07320
- Remove the cause, then acknowledge the fault in one of four ways: through bit 7 of PROFIdrive control word 1 (r2090.7), through a digital input set for acknowledgement, from the operator panel, or by switching the inverter's supply off and on.
- Faults found by the inverter's own monitoring of its hardware and firmware can only be acknowledged by switching the supply voltage off and on.
- Alarms need no acknowledgement: they disappear once the cause is removed.
Clear it once. If F07320 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How automatic restart limit faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Read the fault history to find the fault that triggered the restarts.
- 02Fix that fault before clearing this one.
05 / Repair
When F07320 means a repair
This code is never the root cause on its own.
If F07320 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.
06 / Other drives
Automatic restart limit: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F35 Maximum number of auto restart attempts exceeded |
| Siemens MICROMASTER 440 | F0035 Restart after n |
| Allen-Bradley PowerFlex 525 | F033 Auto Rstrt Tries |
| ABB ACS355 | A2013 AUTORESET |
| Yaskawa V1000 | SEr Too Many Speed Search Restarts |
| Yaskawa A1000 | SEr Too Many Speed Search Restarts |
| Yaskawa GA500 | SEr Speed Search Retries Exceeded |
| Siemens MICROMASTER 420 | F0035 Restart after n · A0571 Auto restart after fault present |
| Siemens MICROMASTER 430 | F0035 Restart after n · A0571 Auto restart after fault present |
| Mitsubishi Electric FR-D700 | E.RET Retry count excess |
07 / More codes
Other SINAMICS G120 codes
Source
Siemens, SINAMICS G120 Converter with the CU240B-2 and CU240E-2 Control Units, Operating Instructions, 04/2018, FW V4.7 SP10, A5E34259001B AF, 8.6 List of alarms and faults (Table 8-7, the most important alarms and faults).
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007