SEr on the Yaskawa GA500 is the “Speed Search Retries Exceeded” fault. A fault shuts off the drive's output and the motor coasts to a stop (some faults let you choose the stopping method). ALM/ERR stays lit, a terminal set to H2-01 to H2-03 = E activates, and the drive will not run until the fault is reset.
The drive tried to restart itself the number of times it is allowed to and gave up. The original fault is still there, and it is the one to find.
- Code
- SEr
- Type
- Fault (stops the drive)
- Drive
- Yaskawa GA500
- Kind of fault
- Automatic restart limit
01 / Causes
What causes SEr
- Speed search parameters set wrongly, or the motor coasting against the run command's direction.
02 / Checks
What to check for SEr
In the order Yaskawa gives them.
- 01Lower b3-10, raise b3-17 and b3-18, and do Auto-Tuning again.
- 02Set b3-14 = 1 (Bi-directional Speed Search).
Also in the manual
- Detected when speed search restarts exceed b3-19.
03 / Clearing it
How to clear SEr
- Remove the cause, then reset in one of three ways: the reset key on the keypad while the code is shown, a multi-function input set to H1-xx = 14 (terminal S4 by default), or switching off the main circuit power and switching it back on once the keypad display has gone out.
- A fault will not reset while a run command is active from the terminals or a communication option; the keypad shows CrST until the run command is removed.
- oL1 resets only once monitor U4-16 (Motor oL1 Level) is below 100.
Clear it once. If SEr comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How automatic restart limit faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Read the fault history to find the fault that triggered the restarts.
- 02Fix that fault before clearing this one.
05 / Repair
When SEr means a repair
This code is never the root cause on its own.
If SEr keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.
06 / Other drives
Automatic restart limit: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F35 Maximum number of auto restart attempts exceeded |
| Siemens SINAMICS G120 | F07320 Automatic restart aborted · A07321 Automatic restart active |
| Siemens MICROMASTER 440 | F0035 Restart after n |
| Allen-Bradley PowerFlex 525 | F033 Auto Rstrt Tries |
| ABB ACS355 | A2013 AUTORESET |
| Yaskawa V1000 | SEr Too Many Speed Search Restarts |
| Yaskawa A1000 | SEr Too Many Speed Search Restarts |
| Siemens MICROMASTER 420 | F0035 Restart after n · A0571 Auto restart after fault present |
| Siemens MICROMASTER 430 | F0035 Restart after n · A0571 Auto restart after fault present |
| Mitsubishi Electric FR-D700 | E.RET Retry count excess |
07 / More codes
Other GA500 codes
Source
Yaskawa, GA500 Drive Technical Reference, C, SIEP C710617 52, 7 Troubleshooting (7.4 to 7.7, 7.9).
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007