MachineryFix

Yaskawa AC drive (VFD) · fault code

V1000 SEr: Too Many Speed Search Restarts

SEr on the Yaskawa V1000 is the “Too Many Speed Search Restarts” fault. A fault interrupts the drive's output and the motor coasts to a stop (unless set to stop another way). The drive stays inoperable until the fault is reset, and a digital output set for fault (H2-oo = E) closes.

The drive tried to restart itself the number of times it is allowed to and gave up. The original fault is still there, and it is the one to find.

Code
SEr
Type
Fault (stops the drive)
Drive
Yaskawa V1000
Kind of fault
Automatic restart limit

01 / Causes

What causes SEr

  • The number of Speed Search restarts went above b3-19: the Speed Search settings are wrong, or the motor is coasting against the run command's direction.

02 / Checks

What to check for SEr

In the order Yaskawa gives them.

  1. 01Reduce the Speed Search detection compensation gain (b3-10), increase the Speed Search current (b3-17) and detection time (b3-18), and repeat Auto-Tuning.
  2. 02If the motor coasts in the opposite direction, enable bi-directional Speed Search (b3-14 = 1).

03 / Clearing it

How to clear SEr

  • Fix the cause, then reset with the reset key on the digital operator, or by closing and opening terminal S4, which is the fault reset input by default.
  • If neither clears it, switch off the drive's main power and switch it back on once the operator display has gone out.
  • Some faults need a condition met before they reset: oL1 cannot be reset until monitor U4-16 is below 100.

Clear it once. If SEr comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How automatic restart limit faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Read the fault history to find the fault that triggered the restarts.
  2. 02Fix that fault before clearing this one.

05 / Repair

When SEr means a repair

This code is never the root cause on its own.

If SEr keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.

06 / Other drives

Automatic restart limit: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F35 Maximum number of auto restart attempts exceeded
Siemens SINAMICS G120F07320 Automatic restart aborted · A07321 Automatic restart active
Siemens MICROMASTER 440F0035 Restart after n
Allen-Bradley PowerFlex 525F033 Auto Rstrt Tries
ABB ACS355A2013 AUTORESET
Yaskawa A1000SEr Too Many Speed Search Restarts
Yaskawa GA500SEr Speed Search Retries Exceeded
Siemens MICROMASTER 420F0035 Restart after n · A0571 Auto restart after fault present
Siemens MICROMASTER 430F0035 Restart after n · A0571 Auto restart after fault present
Mitsubishi Electric FR-D700E.RET Retry count excess

07 / More codes

Other V1000 codes

Source

Yaskawa, YASKAWA AC Drive V1000 Technical Manual, 18F, SIEP C710606 18, 6.4 Fault Detection.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

SEr won't clear? Get a technician who knows the V1000.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.