SINAMICS G120 A07015: Motor temperature sensor alarm

A07015 on the Siemens SINAMICS G120 is the “Motor temperature sensor alarm” alarm. An alarm has no direct effect on the inverter. It disappears once the cause is removed and needs no acknowledgement.

The drive has lost the signal from a temperature sensor: the heat sink sensor inside the drive, or the motor's own sensor. Without it the drive cannot protect itself or the motor.

Code
A07015
Type
Alarm (warning)
Drive
Siemens SINAMICS G120, CU240B-2, CU240E-2
Kind of fault
Temperature sensor signal

01 / Causes

What causes A07015

Siemens's table names this alarm and lists what to do, but gives no separate cause. The checks below are the ones it lists; the section on tracing temperature sensor signal faults explains where it usually comes from.

02 / Checks

What to check for A07015

In the order Siemens gives them.

  1. 01Check the sensor is connected correctly.
  2. 02Check the parameter assignment (p0601).

03 / Clearing it

How to clear A07015

An alarm has no direct effect on the inverter. It disappears once the cause is removed and needs no acknowledgement.

If A07015 stays on, work through the checks above: an alarm that is ignored often becomes a fault that stops the machine.

04 / On site

How temperature sensor signal faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01For a motor sensor, check its wiring to the drive and measure the sensor's resistance.
  2. 02For the drive's own heat sink sensor, there is nothing to adjust from outside.

05 / Repair

When A07015 means a repair

A lost heat sink sensor signal inside the drive needs the unit opened and repaired.

If A07015 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.

06 / Other drives

Temperature sensor signal: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F12 Inverter temperature signal lost · A507 Inverter temperature signal lost
Siemens MICROMASTER 440F0012 No inverter temperature signal · F0015 No motor temperature signal
ABB ACS355F0018 THERM FAIL
Delta VFD-EcF3.4 IGBT overheat (temperature sensor) · cF3.5 Power board overheat (temperature sensor)
Delta C2000tH1o IGBT temperature detection failure · tH2o Capacitor hardware error
Schneider Electric Altivar ATV320INFB Internal error 11 (Temperature) · PTFL DI6=PTC probe error
Yaskawa A1000THo Thermistor Disconnect
Siemens MICROMASTER 430F0012 No inverter temperature signal · F0015 No motor temperature signal
Mitsubishi Electric FR-D700E.PTC PTC thermistor operation
Danfoss VLT Micro Drive FC 51Alarm 11 Motor thermistor over temperature

07 / More codes

Other SINAMICS G120 codes

Source

Siemens, SINAMICS G120 Converter with the CU240B-2 and CU240E-2 Control Units, Operating Instructions, 04/2018, FW V4.7 SP10, A5E34259001B AF, 8.6 List of alarms and faults (Table 8-7, the most important alarms and faults).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

A07015 won't clear? Get a technician who knows the SINAMICS G120.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.