F60 on the Siemens SINAMICS V20 is the “Asic timeout” fault. A fault stops the inverter's output; the motor will not run again until the fault is cleared.
The drive's own electronics reported a problem: a self-test, a processor, an internal link or the power module's identification. There is nothing in the machine to fix.
- Code
- F60
- Type
- Fault (stops the drive)
- Drive
- Siemens SINAMICS V20
- Kind of fault
- Internal drive fault
01 / Causes
What causes F60
- An internal communications failure.
02 / Checks
What to check for F60
In the order Siemens gives them.
- 01Check the inverter.
- 02If the fault appears sporadically, suspect electrical noise: check and improve EMC, and use an EMC filter.
Also in the manual
- r0949 = 0: hardware reported a link failure; r0949 = 1: software reported a link failure.
03 / Clearing it
How to clear F60
- Clear or acknowledge a fault from the BOP, or externally if the inverter is set up for it.
- Holding the function key for more than two seconds shows the inverter's status at the moment of the fault.
- Some faults (F64, F350) can only be cleared by switching the power off and on, and F5 cannot be cleared until the inverter's overload utilisation has fallen below its warning level.
Clear it once. If F60 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How internal drive fault faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Power-cycle the drive and note whether the fault returns.
- 02Check for electrical noise: screened cables, earthing and an EMC filter where the manual calls for one.
- 03Note the fault value the drive shows with the code; the manufacturer uses it to narrow the cause.
05 / Repair
When F60 means a repair
If the fault survives a power cycle, the drive needs a bench repair or replacement.
If F60 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.
06 / Other drives
Internal drive fault: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS G120 | F01000 Software error in the CU · F01001 Floating point exception · F01015 Software error in the CU · F01018 Power-up aborted more than once · F01054 System limit exceeded · F01205 CU: Time slice overflow |
| Siemens SINAMICS V90 | F1000 Internal software error · F1001 FloatingPoint exception · F1002 Internal software error · F1003 Acknowledgement delay when accessing the memory · F1015 Internal software error · F1018 Booting has been interrupted several times |
| Siemens MICROMASTER 440 | F0040 Fault, for automatic calibration · F0052 Power stack fault · F0053 I/O EEPROM fault · F0054 Incorrect I/O module · F0060 Asic time slice overflow · F0101 Stack overflow |
| Allen-Bradley PowerFlex 525 | F070 Power Unit · F105 C Connect Err · F106 Incompat C-P · F107 Replaced C-P · F109 Mismatch C-P · F110 Keypad Membrane |
| ABB ACS355 | F0021 CURR MEAS · F0027 CONFIG FILE · F0036 INCOMPATIBLE SW · F0101 SERF CORRUPT · F0103 SERF MACRO · F0201 DSP T1 OVERLOAD |
| Delta VFD-E | HPF1 CC, OC hardware protection failure · HPF2 OV hardware protection failure · HPF3 GFF hardware protection failure · HPF4 OC hardware protection failure · codE Software protection failure · cF3.0 U-phase error |
| Delta C2000 | cd1 U-phase error · cd2 V-phase error · cd3 W-phase error · Hd0 cc hardware failure · Hd1 oc hardware error · Hd2 ov hardware error |
| Delta ASDA-B2 | AL012 Adjustment error · AL555 System failure · AL880 System failure |
| Hitachi WJ200 | E10 Current detection error · E11 CPU error · E22 CPU communication error · E25 Main circuit error · E30 Driver error · E63 Option error |
| Schneider Electric Altivar ATV320 | CRF1 Precharge capacitor error · ILF Internal link error · INF1 Internal error 1 (Rating) · INF2 Internal error 2 (Soft) · INF3 Internal error 3 (Intern Comm) · INF4 Internal error 4 (Manufacturing) |
| INVT Goodrive20 (GD20) | ItE Current detection fault |
| Yaskawa V1000 | CoF Current Offset Fault · CPF02 A/D Conversion Error · CPF03 PWM Data Error · CPF07 Terminal Board Communications Error · CPF08 EEPROM Serial Communication Fault · CPF11 RAM Fault |
| Yaskawa A1000 | CoF Current Offset Fault · CPF02 A/D Conversion Error · CPF03 Control Board Connection Error · CPF07 Terminal Board Connection Error · CPF08 Terminal Board Connection Error · CPF11 RAM Fault |
| Yaskawa GA500 | bAT Keypad Battery Low Voltage · CoF Current Offset Fault · CPF00 Control Circuit Error · CPF01 Control Circuit Error · CPF02 Control Circuit Error · CPF03 Control Circuit Error |
| Siemens MICROMASTER 420 | F0052 Power stack fault · F0060 Asic time slice overflow · F0101 Stack overflow · F0450 Failure BIST tests · A0600 RTOS data loss alarm |
| Siemens MICROMASTER 430 | F0052 Power stack fault · F0054 Incorrect I/O module · F0060 Asic time slice overflow · F0101 Stack overflow · F0450 Failure BIST tests · A0522 Read I2C, time exceeded |
| Siemens SINAMICS G110 | F0052 Power stack fault · F0060 Asic timeout · F0100 Watchdog reset · F0101 Stack overflow |
| INVT Goodrive200A (GD200A) | ItE Current detection fault |
| Mitsubishi Electric FR-D700 | E.CPU CPU fault · E.IOH Inrush current limit circuit fault |
| Danfoss VLT Micro Drive FC 51 | Alarm 38 Internal fault · Alarm 46 Gate drive voltage fault · Alarm 47 Control voltage fault |
07 / More codes
Other SINAMICS V20 codes
Source
Siemens, SINAMICS V20 Inverter Operating Instructions, 01/2018, A5E34559884-009, Chapter 9, Faults and alarms.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007