MachineryFix

Schneider Electric AC drive (VFD) · fault code

Altivar ATV320 INF3: Internal error 3 (Intern Comm)

INF3 on the Schneider Electric Altivar ATV320 is the “Internal error 3 (Intern Comm)” fault. A detected error stops the drive until it is cleared, in the way the manual gives for that code.

The drive's own electronics reported a problem: a self-test, a processor, an internal link or the power module's identification. There is nothing in the machine to fix.

Code
INF3
Type
Fault (stops the drive)
Drive
Schneider Electric Altivar ATV320
Kind of fault
Internal drive fault

01 / Causes

What causes INF3

  • Communication between the internal cards was interrupted.

02 / Checks

What to check for INF3

In the order Schneider Electric gives them.

  1. 01Check the internal connections.
  2. 02Contact Schneider Electric Product Support.

Also in the manual

  • Clears only with a power reset, after the cause is removed.

03 / Clearing it

How to clear INF3

  • Remove the cause first. A resettable error can then be cleared by switching the drive off until the display goes out completely and back on, automatically by the Auto Fault Reset (ATR) function, through an input or control bit assigned to Fault reset (RST), or with the STOP/RESET key on the graphic display terminal when it is the active command channel.
  • Some codes need a power reset (ANF, ASF, BLF, BRF, CRF1, EEF1, EEF2, FCF1, HDF, ILF, the INF codes, SAFF, SOF, SPF); ASF, BRF, SOF, SPF and TNF can also be cleared remotely with Fault Reset Assign (RSF).
  • For an error that cannot be reset, Schneider's steps are: disconnect all power, including external control power; lock the disconnects open; wait 15 minutes for the DC bus capacitors to discharge; check the DC bus between PA/+ and PC/- is below 42 V DC; find and fix the cause; then restore power to confirm.

Clear it once. If INF3 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How internal drive fault faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Power-cycle the drive and note whether the fault returns.
  2. 02Check for electrical noise: screened cables, earthing and an EMC filter where the manual calls for one.
  3. 03Note the fault value the drive shows with the code; the manufacturer uses it to narrow the cause.

05 / Repair

When INF3 means a repair

If the fault survives a power cycle, the drive needs a bench repair or replacement.

If INF3 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Schneider Electric drives, and they arrive knowing what to look for.

06 / Other drives

Internal drive fault: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F52 Inverter software fault · F60 Asic timeout · F100 Watchdog reset · F101 Stack overflow · F200 Script error · F350 Configuration vector for the inverter failed
Siemens SINAMICS G120F01000 Software error in the CU · F01001 Floating point exception · F01015 Software error in the CU · F01018 Power-up aborted more than once · F01054 System limit exceeded · F01205 CU: Time slice overflow
Siemens SINAMICS V90F1000 Internal software error · F1001 FloatingPoint exception · F1002 Internal software error · F1003 Acknowledgement delay when accessing the memory · F1015 Internal software error · F1018 Booting has been interrupted several times
Siemens MICROMASTER 440F0040 Fault, for automatic calibration · F0052 Power stack fault · F0053 I/O EEPROM fault · F0054 Incorrect I/O module · F0060 Asic time slice overflow · F0101 Stack overflow
Allen-Bradley PowerFlex 525F070 Power Unit · F105 C Connect Err · F106 Incompat C-P · F107 Replaced C-P · F109 Mismatch C-P · F110 Keypad Membrane
ABB ACS355F0021 CURR MEAS · F0027 CONFIG FILE · F0036 INCOMPATIBLE SW · F0101 SERF CORRUPT · F0103 SERF MACRO · F0201 DSP T1 OVERLOAD
Delta VFD-EHPF1 CC, OC hardware protection failure · HPF2 OV hardware protection failure · HPF3 GFF hardware protection failure · HPF4 OC hardware protection failure · codE Software protection failure · cF3.0 U-phase error
Delta C2000cd1 U-phase error · cd2 V-phase error · cd3 W-phase error · Hd0 cc hardware failure · Hd1 oc hardware error · Hd2 ov hardware error
Delta ASDA-B2AL012 Adjustment error · AL555 System failure · AL880 System failure
Hitachi WJ200E10 Current detection error · E11 CPU error · E22 CPU communication error · E25 Main circuit error · E30 Driver error · E63 Option error
INVT Goodrive20 (GD20)ItE Current detection fault
Yaskawa V1000CoF Current Offset Fault · CPF02 A/D Conversion Error · CPF03 PWM Data Error · CPF07 Terminal Board Communications Error · CPF08 EEPROM Serial Communication Fault · CPF11 RAM Fault
Yaskawa A1000CoF Current Offset Fault · CPF02 A/D Conversion Error · CPF03 Control Board Connection Error · CPF07 Terminal Board Connection Error · CPF08 Terminal Board Connection Error · CPF11 RAM Fault
Yaskawa GA500bAT Keypad Battery Low Voltage · CoF Current Offset Fault · CPF00 Control Circuit Error · CPF01 Control Circuit Error · CPF02 Control Circuit Error · CPF03 Control Circuit Error
Siemens MICROMASTER 420F0052 Power stack fault · F0060 Asic time slice overflow · F0101 Stack overflow · F0450 Failure BIST tests · A0600 RTOS data loss alarm
Siemens MICROMASTER 430F0052 Power stack fault · F0054 Incorrect I/O module · F0060 Asic time slice overflow · F0101 Stack overflow · F0450 Failure BIST tests · A0522 Read I2C, time exceeded
Siemens SINAMICS G110F0052 Power stack fault · F0060 Asic timeout · F0100 Watchdog reset · F0101 Stack overflow
INVT Goodrive200A (GD200A)ItE Current detection fault
Mitsubishi Electric FR-D700E.CPU CPU fault · E.IOH Inrush current limit circuit fault
Danfoss VLT Micro Drive FC 51Alarm 38 Internal fault · Alarm 46 Gate drive voltage fault · Alarm 47 Control voltage fault

07 / More codes

Other Altivar ATV320 codes

Source

Schneider Electric, Altivar Machine ATV320 Programming Manual, 04/2025, NVE41295.06, Diagnostics and Troubleshooting.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Schneider Electric and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

INF3 won't clear? Get a technician who knows the Altivar ATV320.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.