MachineryFix

Yaskawa AC drive (VFD) · fault code

V1000 CPF02: A/D Conversion Error

CPF02 on the Yaskawa V1000 is the “A/D Conversion Error” fault. A fault interrupts the drive's output and the motor coasts to a stop (unless set to stop another way). The drive stays inoperable until the fault is reset, and a digital output set for fault (H2-oo = E) closes.

The drive's own electronics reported a problem: a self-test, a processor, an internal link or the power module's identification. There is nothing in the machine to fix.

Code
CPF02
Type
Fault (stops the drive)
Drive
Yaskawa V1000
Kind of fault
Internal drive fault

01 / Causes

What causes CPF02

  • An A/D conversion error: a damaged control circuit, shorted control terminals (+V, AC), or too much current into a control terminal.

02 / Checks

What to check for CPF02

In the order Yaskawa gives them.

  1. 01Cycle power to the drive; if the fault continues, replace the drive.
  2. 02Check the control circuit wiring for errors and correct it; check the speed potentiometer's resistance and wiring.
  3. 03Check the input current and keep the current into terminal +V to 20 mA.

03 / Clearing it

How to clear CPF02

  • Fix the cause, then reset with the reset key on the digital operator, or by closing and opening terminal S4, which is the fault reset input by default.
  • If neither clears it, switch off the drive's main power and switch it back on once the operator display has gone out.
  • Some faults need a condition met before they reset: oL1 cannot be reset until monitor U4-16 is below 100.

Clear it once. If CPF02 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How internal drive fault faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Power-cycle the drive and note whether the fault returns.
  2. 02Check for electrical noise: screened cables, earthing and an EMC filter where the manual calls for one.
  3. 03Note the fault value the drive shows with the code; the manufacturer uses it to narrow the cause.

05 / Repair

When CPF02 means a repair

If the fault survives a power cycle, the drive needs a bench repair or replacement.

If CPF02 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.

06 / Other drives

Internal drive fault: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F52 Inverter software fault · F60 Asic timeout · F100 Watchdog reset · F101 Stack overflow · F200 Script error · F350 Configuration vector for the inverter failed
Siemens SINAMICS G120F01000 Software error in the CU · F01001 Floating point exception · F01015 Software error in the CU · F01018 Power-up aborted more than once · F01054 System limit exceeded · F01205 CU: Time slice overflow
Siemens SINAMICS V90F1000 Internal software error · F1001 FloatingPoint exception · F1002 Internal software error · F1003 Acknowledgement delay when accessing the memory · F1015 Internal software error · F1018 Booting has been interrupted several times
Siemens MICROMASTER 440F0040 Fault, for automatic calibration · F0052 Power stack fault · F0053 I/O EEPROM fault · F0054 Incorrect I/O module · F0060 Asic time slice overflow · F0101 Stack overflow
Allen-Bradley PowerFlex 525F070 Power Unit · F105 C Connect Err · F106 Incompat C-P · F107 Replaced C-P · F109 Mismatch C-P · F110 Keypad Membrane
ABB ACS355F0021 CURR MEAS · F0027 CONFIG FILE · F0036 INCOMPATIBLE SW · F0101 SERF CORRUPT · F0103 SERF MACRO · F0201 DSP T1 OVERLOAD
Delta VFD-EHPF1 CC, OC hardware protection failure · HPF2 OV hardware protection failure · HPF3 GFF hardware protection failure · HPF4 OC hardware protection failure · codE Software protection failure · cF3.0 U-phase error
Delta C2000cd1 U-phase error · cd2 V-phase error · cd3 W-phase error · Hd0 cc hardware failure · Hd1 oc hardware error · Hd2 ov hardware error
Delta ASDA-B2AL012 Adjustment error · AL555 System failure · AL880 System failure
Hitachi WJ200E10 Current detection error · E11 CPU error · E22 CPU communication error · E25 Main circuit error · E30 Driver error · E63 Option error
Schneider Electric Altivar ATV320CRF1 Precharge capacitor error · ILF Internal link error · INF1 Internal error 1 (Rating) · INF2 Internal error 2 (Soft) · INF3 Internal error 3 (Intern Comm) · INF4 Internal error 4 (Manufacturing)
INVT Goodrive20 (GD20)ItE Current detection fault
Yaskawa A1000CoF Current Offset Fault · CPF02 A/D Conversion Error · CPF03 Control Board Connection Error · CPF07 Terminal Board Connection Error · CPF08 Terminal Board Connection Error · CPF11 RAM Fault
Yaskawa GA500bAT Keypad Battery Low Voltage · CoF Current Offset Fault · CPF00 Control Circuit Error · CPF01 Control Circuit Error · CPF02 Control Circuit Error · CPF03 Control Circuit Error
Siemens MICROMASTER 420F0052 Power stack fault · F0060 Asic time slice overflow · F0101 Stack overflow · F0450 Failure BIST tests · A0600 RTOS data loss alarm
Siemens MICROMASTER 430F0052 Power stack fault · F0054 Incorrect I/O module · F0060 Asic time slice overflow · F0101 Stack overflow · F0450 Failure BIST tests · A0522 Read I2C, time exceeded
Siemens SINAMICS G110F0052 Power stack fault · F0060 Asic timeout · F0100 Watchdog reset · F0101 Stack overflow
INVT Goodrive200A (GD200A)ItE Current detection fault
Mitsubishi Electric FR-D700E.CPU CPU fault · E.IOH Inrush current limit circuit fault
Danfoss VLT Micro Drive FC 51Alarm 38 Internal fault · Alarm 46 Gate drive voltage fault · Alarm 47 Control voltage fault

07 / More codes

Other V1000 codes

Source

Yaskawa, YASKAWA AC Drive V1000 Technical Manual, 18F, SIEP C710606 18, 6.4 Fault Detection.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007