STo on the Yaskawa V1000 is the “Motor Pull Out or Step Out Detection” fault. A fault interrupts the drive's output and the motor coasts to a stop (unless set to stop another way). The drive stays inoperable until the fault is reset, and a digital output set for fault (H2-oo = E) closes.
The drive could not get the motor to follow the commanded speed: it sat at its current limit for too long. The load is too heavy for the ramp, the motor is jammed, or the motor is connected or set up wrongly.
- Code
- STo
- Type
- Fault (stops the drive)
- Drive
- Yaskawa V1000
- Kind of fault
- Motor stall
01 / Causes
What causes STo
- The PM motor pulled out of step: it went past its pull-out torque.
- A wrong motor code, too heavy a load or load inertia, or acceleration and deceleration too short.
02 / Checks
What to check for STo
In the order Yaskawa gives them.
- 01Enter the correct motor code in E5-01; for special motors, enter all E5 parameters from the motor's test report.
- 02Increase n8-55 (load inertia for PM) and n8-51 (pull-in current during accel/decel).
- 03Reduce the load or use a larger motor or drive.
- 04Lengthen the acceleration and deceleration times (C1-01 to C1-08) and the S-curve (C2-01).
03 / Clearing it
How to clear STo
- Fix the cause, then reset with the reset key on the digital operator, or by closing and opening terminal S4, which is the fault reset input by default.
- If neither clears it, switch off the drive's main power and switch it back on once the operator display has gone out.
- Some faults need a condition met before they reset: oL1 cannot be reset until monitor U4-16 is below 100.
Clear it once. If STo comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How motor stall faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check the load turns freely and nothing is jammed.
- 02Lengthen the acceleration time and check the current limit setting.
- 03Check motor connections (star or delta) against the rating plate and the drive's motor data.
05 / Repair
When STo means a repair
A free-turning load, correct setup and repeated stalls point at a motor winding fault or a drive output problem.
If STo keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.
06 / Other drives
Motor stall: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS G120 | F07900 Motor blocked · F07902 Motor stalled · A07903 Motor speed deviation |
| Siemens SINAMICS V90 | F7450 Standstill monitoring has responded · F7452 Following error too high · F7900 Motor blocked/speed controller at its limit |
| Siemens MICROMASTER 440 | F0453 Motor stalled |
| Allen-Bradley PowerFlex 525 | F006 Motor Stalled |
| ABB ACS355 | F0012 MOTOR STALL · A2012 MOTOR STALL |
| Delta C2000 | oSL Over slip error · SdRv Reverse direction of the speed feedback · SdOr Over speed rotation feedback · SdDe Large deviation of speed feedback · SfLK PMLess shaft lock |
| Delta ASDA-B2 | AL009 Excessive deviation of position command |
| Schneider Electric Altivar ATV320 | ANF Load slipping error · SSF Torque limitation error |
| INVT Goodrive20 (GD20) | dEu Speed deviation fault |
| Yaskawa A1000 | LSo LSo Fault · STo Pull-Out Detection |
| Yaskawa GA500 | LSo Low Speed Motor Step-Out · STPo Motor Step-Out Detected |
| Mitsubishi Electric FR-D700 | E.OLT Stall prevention stop |
| Danfoss VLT Micro Drive FC 51 | Warning 12 Torque limit |
07 / More codes
Other V1000 codes
Source
Yaskawa, YASKAWA AC Drive V1000 Technical Manual, 18F, SIEP C710606 18, 6.4 Fault Detection.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007