F111 on the Allen-Bradley PowerFlex 525 is the “Safety Hardware” fault. A fault stops the drive; it will not restart until the fault is cleared.
The drive's safe torque off inputs are open, so it cannot produce torque. Either the safety circuit is doing its job (an e-stop, a guard), or the inputs are not wired or jumpered.
- Code
- F111
- Type
- Fault (stops the drive)
- Drive
- Allen-Bradley PowerFlex 525, PowerFlex 523
- Kind of fault
- Safety input
01 / Causes
What causes F111
Rockwell Automation's table names this fault and lists what to do, but gives no separate cause. The checks below are the ones it lists; the section on tracing safety input faults explains where it usually comes from.
02 / Checks
What to check for F111
In the order Rockwell Automation gives them.
- 01Check the safety input signals. If the safety function is not used, check the jumper across I/O terminals S1, S2 and S+ is fitted and tight.
- 02Replace the control module if the fault cannot be cleared.
Also in the manual
- This fault does not apply to the PowerFlex 523, only the PowerFlex 525.
03 / Clearing it
How to clear F111
- Rockwell's parameter A551 [Fault Clear] resets a fault when set to 1 (Reset Fault); setting it to 2 (Clear Buffer) also clears the fault queue.
- Correct the cause first: F033 means the drive has already used up its automatic restart attempts on a fault that is still there.
Clear it once. If F111 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How safety input faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check the e-stop, guard switches and safety relay feeding the safety inputs.
- 02If the machine does not use the safety function, check the manufacturer's jumper is fitted and tight.
05 / Repair
When F111 means a repair
Never bypass a working safety circuit. A safety input fault that stays with the circuit healthy needs the drive's control module checked.
If F111 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Allen-Bradley drives, and they arrive knowing what to look for.
06 / Other drives
Safety input: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS G120 | F01600 STOP A initiated · F01625 Sign-of-life error in the Safety data · F01650 Acceptance test required · F01659 Write task for parameter rejected · F30600 STOP A triggered · A01666 Static 1 signal at the F-DI for safe acknowledgement |
| Siemens SINAMICS V90 | F1611 SI CU: Defect detected · A52902 Emergency missing |
| ABB ACS355 | F0044 SAFE TORQUE OFF · F0045 STO1 LOST · F0046 STO2 LOST · A2023 EMERGENCY STOP · A2035 SAFE TORQUE OFF |
| Delta C2000 | STL1 STO Loss 1 · S1 Emergency stop for external safety · STO Safety Torque Off function active · STL2 STO Loss 2 · STL3 STO Loss 3 |
| Delta ASDA-B2 | AL013 Emergency stop |
| Hitachi WJ200 | E37 Safe Stop |
| Schneider Electric Altivar ATV320 | SAFF Safety function detected error |
| Yaskawa V1000 | Hbb Safe Disable Signal Input · HbbF Safe Disable Signal Input |
| Yaskawa A1000 | Hbb Safe Disable Signal Input · HbbF Safe Disable Signal Input |
| Yaskawa GA500 | SCF Safety Circuit Fault · SToF Safe Torque OFF Hardware |
| Mitsubishi Electric FR-D700 | E.SAF Safety circuit fault · SA Safety stop |
07 / More codes
Other PowerFlex 525 codes
Source
Rockwell Automation, PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start, November 2017, 520-QS001B-EN-E, Fault Codes.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Allen-Bradley and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007