PowerFlex 525 F059: Safety Open

F059 on the Allen-Bradley PowerFlex 525 is the “Safety Open” fault. A fault stops the drive; it will not restart until the fault is cleared.

The drive's safe torque off inputs are open, so it cannot produce torque. Either the safety circuit is doing its job (an e-stop, a guard), or the inputs are not wired or jumpered.

Code
F059
Type
Fault (stops the drive)
Drive
Allen-Bradley PowerFlex 525, PowerFlex 523
Kind of fault
Safety input

01 / Causes

What causes F059

Rockwell Automation's table names this fault and lists what to do, but gives no separate cause. The checks below are the ones it lists; the section on tracing safety input faults explains where it usually comes from.

02 / Checks

What to check for F059

In the order Rockwell Automation gives them.

  1. 01Check the safety input signals.
  2. 02If the safety function is not used, check the jumper across I/O terminals S1, S2 and S+ is fitted and tight.

Also in the manual

  • This fault does not apply to the PowerFlex 523, only the PowerFlex 525.

03 / Clearing it

How to clear F059

  • Rockwell's parameter A551 [Fault Clear] resets a fault when set to 1 (Reset Fault); setting it to 2 (Clear Buffer) also clears the fault queue.
  • Correct the cause first: F033 means the drive has already used up its automatic restart attempts on a fault that is still there.

Clear it once. If F059 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How safety input faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check the e-stop, guard switches and safety relay feeding the safety inputs.
  2. 02If the machine does not use the safety function, check the manufacturer's jumper is fitted and tight.

05 / Repair

When F059 means a repair

Never bypass a working safety circuit. A safety input fault that stays with the circuit healthy needs the drive's control module checked.

If F059 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Allen-Bradley drives, and they arrive knowing what to look for.

06 / Other drives

Safety input: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS G120F01600 STOP A initiated · F01625 Sign-of-life error in the Safety data · F01650 Acceptance test required · F01659 Write task for parameter rejected · F30600 STOP A triggered · A01666 Static 1 signal at the F-DI for safe acknowledgement
Siemens SINAMICS V90F1611 SI CU: Defect detected · A52902 Emergency missing
ABB ACS355F0044 SAFE TORQUE OFF · F0045 STO1 LOST · F0046 STO2 LOST · A2023 EMERGENCY STOP · A2035 SAFE TORQUE OFF
Delta C2000STL1 STO Loss 1 · S1 Emergency stop for external safety · STO Safety Torque Off function active · STL2 STO Loss 2 · STL3 STO Loss 3
Delta ASDA-B2AL013 Emergency stop
Hitachi WJ200E37 Safe Stop
Schneider Electric Altivar ATV320SAFF Safety function detected error
Yaskawa V1000Hbb Safe Disable Signal Input · HbbF Safe Disable Signal Input
Yaskawa A1000Hbb Safe Disable Signal Input · HbbF Safe Disable Signal Input
Yaskawa GA500SCF Safety Circuit Fault · SToF Safe Torque OFF Hardware
Mitsubishi Electric FR-D700E.SAF Safety circuit fault · SA Safety stop

07 / More codes

Other PowerFlex 525 codes

Source

Rockwell Automation, PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start, November 2017, 520-QS001B-EN-E, Fault Codes.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Allen-Bradley and is not its authorised service partner.