F01659 on the Siemens SINAMICS G120 is the “Write task for parameter rejected” fault. A fault generally switches the motor off, and it must be acknowledged before the inverter runs again.
The drive's safe torque off inputs are open, so it cannot produce torque. Either the safety circuit is doing its job (an e-stop, a guard), or the inputs are not wired or jumpered.
- Code
- F01659
- Type
- Fault (stops the drive)
- Drive
- Siemens SINAMICS G120, CU240B-2, CU240E-2
- Kind of fault
- Safety input
01 / Causes
What causes F01659
- The inverter was to be reset to its factory setting, but the safety functions cannot be reset while they are enabled.
02 / Checks
What to check for F01659
In the order Siemens gives them.
- 01From the operator panel: set p0010 = 30 (parameter reset), enter the safety functions password in p9761 if needed, then set p0970 = 5 (reset start safety parameter). The inverter sets p0970 = 5 once it has reset the parameters.
- 02Then reset the inverter to the factory setting again.
03 / Clearing it
How to clear F01659
- Remove the cause, then acknowledge the fault in one of four ways: through bit 7 of PROFIdrive control word 1 (r2090.7), through a digital input set for acknowledgement, from the operator panel, or by switching the inverter's supply off and on.
- Faults found by the inverter's own monitoring of its hardware and firmware can only be acknowledged by switching the supply voltage off and on.
- Alarms need no acknowledgement: they disappear once the cause is removed.
Clear it once. If F01659 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How safety input faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check the e-stop, guard switches and safety relay feeding the safety inputs.
- 02If the machine does not use the safety function, check the manufacturer's jumper is fitted and tight.
05 / Repair
When F01659 means a repair
Never bypass a working safety circuit. A safety input fault that stays with the circuit healthy needs the drive's control module checked.
If F01659 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.
06 / Other drives
Safety input: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V90 | F1611 SI CU: Defect detected · A52902 Emergency missing |
| Allen-Bradley PowerFlex 525 | F059 Safety Open · F111 Safety Hardware |
| ABB ACS355 | F0044 SAFE TORQUE OFF · F0045 STO1 LOST · F0046 STO2 LOST · A2023 EMERGENCY STOP · A2035 SAFE TORQUE OFF |
| Delta C2000 | STL1 STO Loss 1 · S1 Emergency stop for external safety · STO Safety Torque Off function active · STL2 STO Loss 2 · STL3 STO Loss 3 |
| Delta ASDA-B2 | AL013 Emergency stop |
| Hitachi WJ200 | E37 Safe Stop |
| Schneider Electric Altivar ATV320 | SAFF Safety function detected error |
| Yaskawa V1000 | Hbb Safe Disable Signal Input · HbbF Safe Disable Signal Input |
| Yaskawa A1000 | Hbb Safe Disable Signal Input · HbbF Safe Disable Signal Input |
| Yaskawa GA500 | SCF Safety Circuit Fault · SToF Safe Torque OFF Hardware |
| Mitsubishi Electric FR-D700 | E.SAF Safety circuit fault · SA Safety stop |
07 / More codes
Other SINAMICS G120 codes
Source
Siemens, SINAMICS G120 Converter with the CU240B-2 and CU240E-2 Control Units, Operating Instructions, 04/2018, FW V4.7 SP10, A5E34259001B AF, 8.6 List of alarms and faults (Table 8-7, the most important alarms and faults).
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007