A2023 on the ABB ACS355 is the “EMERGENCY STOP” alarm. An alarm warns of a condition without tripping the drive, and the green LED blinks. Some alarms are a normal part of operation, such as A2019 during the motor ID run.
The drive's safe torque off inputs are open, so it cannot produce torque. Either the safety circuit is doing its job (an e-stop, a guard), or the inputs are not wired or jumpered.
- Code
- A2023
- Type
- Alarm (warning)
- Drive
- ABB ACS355
- Kind of fault
- Safety input
01 / Causes
What causes A2023
- The drive received an emergency stop command and is ramping to a stop in the time set by parameter 2208 EMERG DEC TIME.
02 / Checks
What to check for A2023
In the order ABB gives them.
- 01Check it is safe to continue running.
- 02Return the emergency stop push button to its normal position.
03 / Clearing it
How to clear A2023
An alarm warns of a condition without tripping the drive, and the green LED blinks. Some alarms are a normal part of operation, such as A2019 during the motor ID run.
If A2023 stays on, work through the checks above: an alarm that is ignored often becomes a fault that stops the machine.
04 / On site
How safety input faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check the e-stop, guard switches and safety relay feeding the safety inputs.
- 02If the machine does not use the safety function, check the manufacturer's jumper is fitted and tight.
05 / Repair
When A2023 means a repair
Never bypass a working safety circuit. A safety input fault that stays with the circuit healthy needs the drive's control module checked.
If A2023 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on ABB drives, and they arrive knowing what to look for.
06 / Other drives
Safety input: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS G120 | F01600 STOP A initiated · F01625 Sign-of-life error in the Safety data · F01650 Acceptance test required · F01659 Write task for parameter rejected · F30600 STOP A triggered · A01666 Static 1 signal at the F-DI for safe acknowledgement |
| Siemens SINAMICS V90 | F1611 SI CU: Defect detected · A52902 Emergency missing |
| Allen-Bradley PowerFlex 525 | F059 Safety Open · F111 Safety Hardware |
| Delta C2000 | STL1 STO Loss 1 · S1 Emergency stop for external safety · STO Safety Torque Off function active · STL2 STO Loss 2 · STL3 STO Loss 3 |
| Delta ASDA-B2 | AL013 Emergency stop |
| Hitachi WJ200 | E37 Safe Stop |
| Schneider Electric Altivar ATV320 | SAFF Safety function detected error |
| Yaskawa V1000 | Hbb Safe Disable Signal Input · HbbF Safe Disable Signal Input |
| Yaskawa A1000 | Hbb Safe Disable Signal Input · HbbF Safe Disable Signal Input |
| Yaskawa GA500 | SCF Safety Circuit Fault · SToF Safe Torque OFF Hardware |
| Mitsubishi Electric FR-D700 | E.SAF Safety circuit fault · SA Safety stop |
07 / More codes
Other ACS355 codes
Source
ABB, ACS355 user's manual, Rev E, effective 2 November 2020, 3AUA0000066143, Fault tracing.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of ABB and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007