SA on the Mitsubishi Electric FR-D700 is the “Safety stop” alarm. Error messages, warnings and the fan alarm are shown while the inverter keeps its output on.
The drive's safe torque off inputs are open, so it cannot produce torque. Either the safety circuit is doing its job (an e-stop, a guard), or the inputs are not wired or jumpered.
- Code
- SA
- Type
- Alarm (warning)
- Drive
- Mitsubishi Electric FR-D700, FR-D720, FR-D740, FR-D720S, FR-D710W
- Kind of fault
- Safety input
01 / Causes
What causes SA
- The safety stop function is active (the output is shut off).
02 / Checks
What to check for SA
In the order Mitsubishi Electric gives them.
- 01When the safety stop function is not used, check the shorting wires between S1 and SC and between S2 and SC are not disconnected; short across both pairs for the inverter to run.
- 02If SA shows while S1-SC and S2-SC are both shorted with the safety stop function in use (drive enabled), an internal failure may be the cause: check the wiring of S1, S2 and SC, and contact Mitsubishi if the wiring is fine.
Also in the manual
- Mitsubishi lists this as a warning: the inverter's output is not shut off.
03 / Clearing it
How to clear SA
Error messages, warnings and the fan alarm are shown while the inverter keeps its output on.
If SA stays on, work through the checks above: an alarm that is ignored often becomes a fault that stops the machine.
04 / On site
How safety input faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check the e-stop, guard switches and safety relay feeding the safety inputs.
- 02If the machine does not use the safety function, check the manufacturer's jumper is fitted and tight.
05 / Repair
When SA means a repair
Never bypass a working safety circuit. A safety input fault that stays with the circuit healthy needs the drive's control module checked.
If SA keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Mitsubishi Electric drives, and they arrive knowing what to look for.
06 / Other drives
Safety input: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS G120 | F01600 STOP A initiated · F01625 Sign-of-life error in the Safety data · F01650 Acceptance test required · F01659 Write task for parameter rejected · F30600 STOP A triggered · A01666 Static 1 signal at the F-DI for safe acknowledgement |
| Siemens SINAMICS V90 | F1611 SI CU: Defect detected · A52902 Emergency missing |
| Allen-Bradley PowerFlex 525 | F059 Safety Open · F111 Safety Hardware |
| ABB ACS355 | F0044 SAFE TORQUE OFF · F0045 STO1 LOST · F0046 STO2 LOST · A2023 EMERGENCY STOP · A2035 SAFE TORQUE OFF |
| Delta C2000 | STL1 STO Loss 1 · S1 Emergency stop for external safety · STO Safety Torque Off function active · STL2 STO Loss 2 · STL3 STO Loss 3 |
| Delta ASDA-B2 | AL013 Emergency stop |
| Hitachi WJ200 | E37 Safe Stop |
| Schneider Electric Altivar ATV320 | SAFF Safety function detected error |
| Yaskawa V1000 | Hbb Safe Disable Signal Input · HbbF Safe Disable Signal Input |
| Yaskawa A1000 | Hbb Safe Disable Signal Input · HbbF Safe Disable Signal Input |
| Yaskawa GA500 | SCF Safety Circuit Fault · SToF Safe Torque OFF Hardware |
07 / More codes
Other FR-D700 codes
Source
Mitsubishi Electric, FR-D700 Instruction Manual, March 2012 (revision D), IB(NA)-0600368ENG-D, 5.3 Causes and corrective actions.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Mitsubishi Electric and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007