Schneider Electric AC drive (VFD) · fault code

Altivar ATV320 SAFF: Safety function detected error

SAFF on the Schneider Electric Altivar ATV320 is the “Safety function detected error” fault. A detected error stops the drive until it is cleared, in the way the manual gives for that code.

The drive's safe torque off inputs are open, so it cannot produce torque. Either the safety circuit is doing its job (an e-stop, a guard), or the inputs are not wired or jumpered.

Code
SAFF
Type
Fault (stops the drive)
Drive
Schneider Electric Altivar ATV320
Kind of fault
Safety input

01 / Causes

What causes SAFF

  • The debounce time was exceeded.
  • The SS1 threshold was exceeded.
  • The configuration is wrong.
  • An SLS overspeed was detected.

02 / Checks

What to check for SAFF

In the order Schneider Electric gives them.

  1. 01Check the safety functions configuration.
  2. 02See the ATV320 integrated safety functions manual.
  3. 03Contact Schneider Electric Product Support.

Also in the manual

  • Clears only with a power reset, after the cause is removed.

03 / Clearing it

How to clear SAFF

  • Remove the cause first. A resettable error can then be cleared by switching the drive off until the display goes out completely and back on, automatically by the Auto Fault Reset (ATR) function, through an input or control bit assigned to Fault reset (RST), or with the STOP/RESET key on the graphic display terminal when it is the active command channel.
  • Some codes need a power reset (ANF, ASF, BLF, BRF, CRF1, EEF1, EEF2, FCF1, HDF, ILF, the INF codes, SAFF, SOF, SPF); ASF, BRF, SOF, SPF and TNF can also be cleared remotely with Fault Reset Assign (RSF).
  • For an error that cannot be reset, Schneider's steps are: disconnect all power, including external control power; lock the disconnects open; wait 15 minutes for the DC bus capacitors to discharge; check the DC bus between PA/+ and PC/- is below 42 V DC; find and fix the cause; then restore power to confirm.

Clear it once. If SAFF comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How safety input faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check the e-stop, guard switches and safety relay feeding the safety inputs.
  2. 02If the machine does not use the safety function, check the manufacturer's jumper is fitted and tight.

05 / Repair

When SAFF means a repair

Never bypass a working safety circuit. A safety input fault that stays with the circuit healthy needs the drive's control module checked.

If SAFF keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Schneider Electric drives, and they arrive knowing what to look for.

06 / Other drives

Safety input: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS G120F01600 STOP A initiated · F01625 Sign-of-life error in the Safety data · F01650 Acceptance test required · F01659 Write task for parameter rejected · F30600 STOP A triggered · A01666 Static 1 signal at the F-DI for safe acknowledgement
Siemens SINAMICS V90F1611 SI CU: Defect detected · A52902 Emergency missing
Allen-Bradley PowerFlex 525F059 Safety Open · F111 Safety Hardware
ABB ACS355F0044 SAFE TORQUE OFF · F0045 STO1 LOST · F0046 STO2 LOST · A2023 EMERGENCY STOP · A2035 SAFE TORQUE OFF
Delta C2000STL1 STO Loss 1 · S1 Emergency stop for external safety · STO Safety Torque Off function active · STL2 STO Loss 2 · STL3 STO Loss 3
Delta ASDA-B2AL013 Emergency stop
Hitachi WJ200E37 Safe Stop
Yaskawa V1000Hbb Safe Disable Signal Input · HbbF Safe Disable Signal Input
Yaskawa A1000Hbb Safe Disable Signal Input · HbbF Safe Disable Signal Input
Yaskawa GA500SCF Safety Circuit Fault · SToF Safe Torque OFF Hardware
Mitsubishi Electric FR-D700E.SAF Safety circuit fault · SA Safety stop

07 / More codes

Other Altivar ATV320 codes

Source

Schneider Electric, Altivar Machine ATV320 Programming Manual, 04/2025, NVE41295.06, Diagnostics and Troubleshooting.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Schneider Electric and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

SAFF won't clear? Get a technician who knows the Altivar ATV320.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.