SToF on the Yaskawa GA500 is the “Safe Torque OFF Hardware” alarm. A minor fault or alarm leaves the drive running the motor (some let you choose a stopping method) while ALM/ERR flashes. A minor fault activates a terminal set to H2-01 to H2-03 = 10; an alarm gives no signal. No fault reset is needed.
The drive's safe torque off inputs are open, so it cannot produce torque. Either the safety circuit is doing its job (an e-stop, a guard), or the inputs are not wired or jumpered.
- Code
- SToF
- Type
- Alarm (warning)
- Drive
- Yaskawa GA500
- Kind of fault
- Safety input
01 / Causes
What causes SToF
- Only one of terminals H1-HC and H2-HC received the Safe Disable signal: the signal is wired wrongly, or one Safe Disable channel is damaged inside.
02 / Checks
What to check for SToF
In the order Yaskawa gives them.
- 01Make sure the Safe Disable signal reaches terminals H1-HC and H2-HC from the external source.
- 02When Safe Disable is not used, jumper H1-HC and H2-HC.
- 03If a channel is damaged, replace the board or the drive.
03 / Clearing it
How to clear SToF
A minor fault or alarm leaves the drive running the motor (some let you choose a stopping method) while ALM/ERR flashes. A minor fault activates a terminal set to H2-01 to H2-03 = 10; an alarm gives no signal. No fault reset is needed.
If SToF stays on, work through the checks above: an alarm that is ignored often becomes a fault that stops the machine.
04 / On site
How safety input faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check the e-stop, guard switches and safety relay feeding the safety inputs.
- 02If the machine does not use the safety function, check the manufacturer's jumper is fitted and tight.
05 / Repair
When SToF means a repair
Never bypass a working safety circuit. A safety input fault that stays with the circuit healthy needs the drive's control module checked.
If SToF keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.
06 / Other drives
Safety input: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS G120 | F01600 STOP A initiated · F01625 Sign-of-life error in the Safety data · F01650 Acceptance test required · F01659 Write task for parameter rejected · F30600 STOP A triggered · A01666 Static 1 signal at the F-DI for safe acknowledgement |
| Siemens SINAMICS V90 | F1611 SI CU: Defect detected · A52902 Emergency missing |
| Allen-Bradley PowerFlex 525 | F059 Safety Open · F111 Safety Hardware |
| ABB ACS355 | F0044 SAFE TORQUE OFF · F0045 STO1 LOST · F0046 STO2 LOST · A2023 EMERGENCY STOP · A2035 SAFE TORQUE OFF |
| Delta C2000 | STL1 STO Loss 1 · S1 Emergency stop for external safety · STO Safety Torque Off function active · STL2 STO Loss 2 · STL3 STO Loss 3 |
| Delta ASDA-B2 | AL013 Emergency stop |
| Hitachi WJ200 | E37 Safe Stop |
| Schneider Electric Altivar ATV320 | SAFF Safety function detected error |
| Yaskawa V1000 | Hbb Safe Disable Signal Input · HbbF Safe Disable Signal Input |
| Yaskawa A1000 | Hbb Safe Disable Signal Input · HbbF Safe Disable Signal Input |
| Mitsubishi Electric FR-D700 | E.SAF Safety circuit fault · SA Safety stop |
07 / More codes
Other GA500 codes
Source
Yaskawa, GA500 Drive Technical Reference, C, SIEP C710617 52, 7 Troubleshooting (7.4 to 7.7, 7.9).
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007