Schneider Electric AC drive (VFD) · fault code

Altivar ATV320 INFB: Internal error 11 (Temperature)

INFB on the Schneider Electric Altivar ATV320 is the “Internal error 11 (Temperature)” fault. A detected error stops the drive until it is cleared, in the way the manual gives for that code.

The drive has lost the signal from a temperature sensor: the heat sink sensor inside the drive, or the motor's own sensor. Without it the drive cannot protect itself or the motor.

Code
INFB
Type
Fault (stops the drive)
Drive
Schneider Electric Altivar ATV320
Kind of fault
Temperature sensor signal

01 / Causes

What causes INFB

  • The drive's temperature sensor is not working correctly.

02 / Checks

What to check for INFB

In the order Schneider Electric gives them.

  1. 01Replace the drive's temperature sensor.
  2. 02Contact Schneider Electric Product Support.

Also in the manual

  • Clears only with a power reset, after the cause is removed.

03 / Clearing it

How to clear INFB

  • Remove the cause first. A resettable error can then be cleared by switching the drive off until the display goes out completely and back on, automatically by the Auto Fault Reset (ATR) function, through an input or control bit assigned to Fault reset (RST), or with the STOP/RESET key on the graphic display terminal when it is the active command channel.
  • Some codes need a power reset (ANF, ASF, BLF, BRF, CRF1, EEF1, EEF2, FCF1, HDF, ILF, the INF codes, SAFF, SOF, SPF); ASF, BRF, SOF, SPF and TNF can also be cleared remotely with Fault Reset Assign (RSF).
  • For an error that cannot be reset, Schneider's steps are: disconnect all power, including external control power; lock the disconnects open; wait 15 minutes for the DC bus capacitors to discharge; check the DC bus between PA/+ and PC/- is below 42 V DC; find and fix the cause; then restore power to confirm.

Clear it once. If INFB comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How temperature sensor signal faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01For a motor sensor, check its wiring to the drive and measure the sensor's resistance.
  2. 02For the drive's own heat sink sensor, there is nothing to adjust from outside.

05 / Repair

When INFB means a repair

A lost heat sink sensor signal inside the drive needs the unit opened and repaired.

If INFB keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Schneider Electric drives, and they arrive knowing what to look for.

06 / Other drives

Temperature sensor signal: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F12 Inverter temperature signal lost · A507 Inverter temperature signal lost
Siemens SINAMICS G120F07016 Motor temperature sensor fault · A03520 Temperature sensor fault · A07015 Motor temperature sensor alarm · A30920 Temperature sensor fault
Siemens MICROMASTER 440F0012 No inverter temperature signal · F0015 No motor temperature signal
ABB ACS355F0018 THERM FAIL
Delta VFD-EcF3.4 IGBT overheat (temperature sensor) · cF3.5 Power board overheat (temperature sensor)
Delta C2000tH1o IGBT temperature detection failure · tH2o Capacitor hardware error
Yaskawa A1000THo Thermistor Disconnect
Siemens MICROMASTER 430F0012 No inverter temperature signal · F0015 No motor temperature signal
Mitsubishi Electric FR-D700E.PTC PTC thermistor operation
Danfoss VLT Micro Drive FC 51Alarm 11 Motor thermistor over temperature

07 / More codes

Other Altivar ATV320 codes

Source

Schneider Electric, Altivar Machine ATV320 Programming Manual, 04/2025, NVE41295.06, Diagnostics and Troubleshooting.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Schneider Electric and is not its authorised service partner.