A507 on the Siemens SINAMICS V20 is the “Inverter temperature signal lost” alarm. An alarm is a warning: the inverter keeps running, and the alarm clears itself once the condition is gone. Alarms cannot be acknowledged.
The drive has lost the signal from a temperature sensor: the heat sink sensor inside the drive, or the motor's own sensor. Without it the drive cannot protect itself or the motor.
- Code
- A507
- Type
- Alarm (warning)
- Drive
- Siemens SINAMICS V20
- Kind of fault
- Temperature sensor signal
01 / Causes
What causes A507
- The heat sink temperature signal has been lost; the sensor may have come off.
02 / Checks
What to check for A507
In the order Siemens gives them.
- 01Contact Siemens service or change the inverter.
03 / Clearing it
How to clear A507
An alarm is a warning: the inverter keeps running, and the alarm clears itself once the condition is gone. Alarms cannot be acknowledged.
If A507 stays on, work through the checks above: an alarm that is ignored often becomes a fault that stops the machine.
04 / On site
How temperature sensor signal faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01For a motor sensor, check its wiring to the drive and measure the sensor's resistance.
- 02For the drive's own heat sink sensor, there is nothing to adjust from outside.
05 / Repair
When A507 means a repair
A lost heat sink sensor signal inside the drive needs the unit opened and repaired.
If A507 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.
06 / Other drives
Temperature sensor signal: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS G120 | F07016 Motor temperature sensor fault · A03520 Temperature sensor fault · A07015 Motor temperature sensor alarm · A30920 Temperature sensor fault |
| Siemens MICROMASTER 440 | F0012 No inverter temperature signal · F0015 No motor temperature signal |
| ABB ACS355 | F0018 THERM FAIL |
| Delta VFD-E | cF3.4 IGBT overheat (temperature sensor) · cF3.5 Power board overheat (temperature sensor) |
| Delta C2000 | tH1o IGBT temperature detection failure · tH2o Capacitor hardware error |
| Schneider Electric Altivar ATV320 | INFB Internal error 11 (Temperature) · PTFL DI6=PTC probe error |
| Yaskawa A1000 | THo Thermistor Disconnect |
| Siemens MICROMASTER 430 | F0012 No inverter temperature signal · F0015 No motor temperature signal |
| Mitsubishi Electric FR-D700 | E.PTC PTC thermistor operation |
| Danfoss VLT Micro Drive FC 51 | Alarm 11 Motor thermistor over temperature |