E.PTC on the Mitsubishi Electric FR-D700 is the “PTC thermistor operation” fault. On a fault the inverter trips (shuts off its output) and outputs a fault signal until it is reset.
The drive has lost the signal from a temperature sensor: the heat sink sensor inside the drive, or the motor's own sensor. Without it the drive cannot protect itself or the motor.
- Code
- E.PTC
- Type
- Fault (stops the drive)
- Drive
- Mitsubishi Electric FR-D700, FR-D720, FR-D740, FR-D720S, FR-D710W
- Kind of fault
- Temperature sensor signal
01 / Causes
What causes E.PTC
- The resistance of the PTC thermistor connected between terminals 2 and 10 exceeded the Pr. 561 PTC thermistor protection level.
02 / Checks
What to check for E.PTC
In the order Mitsubishi Electric gives them.
- 01Check the PTC thermistor's connection.
- 02Check the Pr. 561 PTC thermistor protection level setting.
- 03Check whether the motor runs under overload, and reduce the load.
Also in the manual
- Does not operate with Pr. 561 at its initial value 9999. On the FR-PU04 it shows as Fault 14.
03 / Clearing it
How to clear E.PTC
- When a fault occurs the inverter trips and outputs a fault signal; warnings, the fan alarm and error messages do not shut off the output.
- Resetting the inverter clears the electronic thermal relay function's accumulated data.
- E.OHT (external thermal relay) does not restart the inverter on its own, even if the relay contacts reset automatically: the inverter has to be reset.
Clear it once. If E.PTC comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How temperature sensor signal faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01For a motor sensor, check its wiring to the drive and measure the sensor's resistance.
- 02For the drive's own heat sink sensor, there is nothing to adjust from outside.
05 / Repair
When E.PTC means a repair
A lost heat sink sensor signal inside the drive needs the unit opened and repaired.
If E.PTC keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Mitsubishi Electric drives, and they arrive knowing what to look for.
06 / Other drives
Temperature sensor signal: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F12 Inverter temperature signal lost · A507 Inverter temperature signal lost |
| Siemens SINAMICS G120 | F07016 Motor temperature sensor fault · A03520 Temperature sensor fault · A07015 Motor temperature sensor alarm · A30920 Temperature sensor fault |
| Siemens MICROMASTER 440 | F0012 No inverter temperature signal · F0015 No motor temperature signal |
| ABB ACS355 | F0018 THERM FAIL |
| Delta VFD-E | cF3.4 IGBT overheat (temperature sensor) · cF3.5 Power board overheat (temperature sensor) |
| Delta C2000 | tH1o IGBT temperature detection failure · tH2o Capacitor hardware error |
| Schneider Electric Altivar ATV320 | INFB Internal error 11 (Temperature) · PTFL DI6=PTC probe error |
| Yaskawa A1000 | THo Thermistor Disconnect |
| Siemens MICROMASTER 430 | F0012 No inverter temperature signal · F0015 No motor temperature signal |
| Danfoss VLT Micro Drive FC 51 | Alarm 11 Motor thermistor over temperature |
07 / More codes
Other FR-D700 codes
Source
Mitsubishi Electric, FR-D700 Instruction Manual, March 2012 (revision D), IB(NA)-0600368ENG-D, 5.3 Causes and corrective actions.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Mitsubishi Electric and is not its authorised service partner.