MachineryFix

ABB AC drive (VFD) · fault code

ACS355 F0018: THERM FAIL

F0018 on the ABB ACS355 is the “THERM FAIL” fault. A fault stops the drive and lights its red LED. The drive will not run again until the fault is reset.

The drive has lost the signal from a temperature sensor: the heat sink sensor inside the drive, or the motor's own sensor. Without it the drive cannot protect itself or the motor.

Code
F0018
Type
Fault (stops the drive)
Drive
ABB ACS355
Kind of fault
Temperature sensor signal

01 / Causes

What causes F0018

  • The drive's temperature is outside the operating range of its internal thermistor.
  • The thermistor that measures the drive's internal temperature is open or short-circuited (an internal fault).

02 / Checks

What to check for F0018

In the order ABB gives them.

  1. 01Check the ambient temperature is not too low.
  2. 02If the thermistor itself has failed, the drive needs replacing.

Also in the manual

  • Over a fieldbus, the drive reports this fault as code 5210.

03 / Clearing it

How to clear F0018

  • Reset with the RESET key on the control panel, through a digital input or fieldbus, or by switching the supply off for a while. Parameter 1604 FAULT RESET SEL chooses the reset source. Once the cause is gone, the motor can be restarted.
  • If the red LED on the drive is blinking rather than steady, the fault can only be reset by switching the drive's power off.
  • Parameters 0401 LAST FAULT, 0412 PREVIOUS FAULT 1 and 0413 PREVIOUS FAULT 2 hold the three most recent faults, and 0404 to 0409 show the drive's operating data at the moment of the latest one.

Clear it once. If F0018 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How temperature sensor signal faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01For a motor sensor, check its wiring to the drive and measure the sensor's resistance.
  2. 02For the drive's own heat sink sensor, there is nothing to adjust from outside.

05 / Repair

When F0018 means a repair

A lost heat sink sensor signal inside the drive needs the unit opened and repaired.

If F0018 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on ABB drives, and they arrive knowing what to look for.

06 / Other drives

Temperature sensor signal: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V20F12 Inverter temperature signal lost · A507 Inverter temperature signal lost
Siemens SINAMICS G120F07016 Motor temperature sensor fault · A03520 Temperature sensor fault · A07015 Motor temperature sensor alarm · A30920 Temperature sensor fault
Siemens MICROMASTER 440F0012 No inverter temperature signal · F0015 No motor temperature signal
Delta VFD-EcF3.4 IGBT overheat (temperature sensor) · cF3.5 Power board overheat (temperature sensor)
Delta C2000tH1o IGBT temperature detection failure · tH2o Capacitor hardware error
Schneider Electric Altivar ATV320INFB Internal error 11 (Temperature) · PTFL DI6=PTC probe error
Yaskawa A1000THo Thermistor Disconnect
Siemens MICROMASTER 430F0012 No inverter temperature signal · F0015 No motor temperature signal
Mitsubishi Electric FR-D700E.PTC PTC thermistor operation
Danfoss VLT Micro Drive FC 51Alarm 11 Motor thermistor over temperature

07 / More codes

Other ACS355 codes

Source

ABB, ACS355 user's manual, Rev E, effective 2 November 2020, 3AUA0000066143, Fault tracing.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of ABB and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

F0018 won't clear? Get a technician who knows the ACS355.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.