AL025 on the Delta ASDA-B2 is the “The internal of the encoder is in error” alarm. This alarm switches the servo off, so the motor is no longer driven until the alarm is cleared.
The speed or position feedback from the encoder is missing or does not agree with what the drive expects.
- Code
- AL025
- Type
- Alarm (stops the drive)
- Drive
- Delta ASDA-B2
- Kind of fault
- Encoder signal
01 / Causes
What causes AL025
- The encoder's internal memory and internal counter are in error.
02 / Checks
What to check for AL025
In the order Delta Electronics gives them.
- 01Check the servo is properly grounded. Delta's corrective action is to connect the UVW connector's green lead to the servo drive's heat sink.
- 02Check the encoder cable runs apart from the power supply and high-current wiring, to keep interference out.
- 03Check the encoder wiring uses shielded cable, with the shield mesh in place.
- 04If it persists, Delta's instruction is to send the drive back to the distributor or contact Delta.
Also in the manual
- ALM output; servo off. Clears after the drive is powered off and on again.
03 / Clearing it
How to clear AL025
- Remove the cause first. Most alarms clear by turning on the alarm reset input, DI.ARST (assigned to DI5 by default).
- Some alarms clear only after the drive is powered off and on: AL004, AL011, AL024 to AL029, AL031 and AL035. AL003 also needs a power cycle, unless P2-66 bit 2 is set so it clears once the voltage is back to normal.
- AL013 clears by itself once the emergency stop input (DI.EMGS) is off. AL014 and AL015 clear with DI.ARST, by switching the servo off, or by moving the motor back off the limit.
- AL099 clears by setting P2-08 to 30, then to 28, and powering the drive off and on. For AL555 and AL880, do nothing to the drive: Delta's instruction is to send it back to the distributor or contact Delta.
Clear it once. If AL025 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How encoder signal faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check the encoder cable and connectors, and that the screen is earthed at the right end.
- 02Check the encoder's supply voltage.
- 03Check the encoder settings (type, pulses per revolution) in the drive.
05 / Repair
When AL025 means a repair
A damaged encoder or cable is replaced; a drive encoder input that has failed needs the drive repaired.
If AL025 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Delta drives, and they arrive knowing what to look for.
06 / Other drives
Encoder signal: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V90 | F7412 Commutation angle incorrect (motor model) · F7430 Changeover to open-loop torque controlled operation not possible · F7431 Changeover to encoderless operation not possible · F7453 Position actual value preprocessing error · F7599 Encoder 1: Adjustment not possible · F31100 Zero mark distance error |
| Siemens MICROMASTER 440 | F0090 Signal loss, encoder · A0590 Alarm, no signals from the speed encoder |
| Allen-Bradley PowerFlex 525 | F091 Encoder Loss |
| ABB ACS355 | F0023 ENCODER ERR · A2024 ENCODER ERROR |
| Delta VFD-E | PGEr PG feedback signal error |
| Delta C2000 | PGF1 PG feedback error · PGF2 PG feedback loss · PGF3 PG feedback stall · PGF4 PG slip error · PGF5 Hardware error of PG card · AboF PG ABZ line off |
| Hitachi WJ200 | E80 Encoder disconnection |
| Schneider Electric Altivar ATV320 | SPF Encoder feedback loss error |
| Yaskawa V1000 | dEv Speed Deviation (for Simple V/f with PG) · oS Overspeed (Simple V/f with PG) · PGo PG Disconnect (for Simple V/f with PG) |
| Yaskawa A1000 | dEv Speed Deviation · dv1 Z Pulse Fault · dv2 Z Pulse Noise Fault Detection · dv3 Inversion Detection · dv4 Inversion Prevention Detection · oS Overspeed |
| Yaskawa GA500 | dEv Speed Deviation · oS Overspeed · PGo Encoder (PG) Feedback Loss |
| Siemens MICROMASTER 430 | F0090 Signal loss, encoder · A0590 Alarm, no signals from the speed encoder |
07 / More codes
Other ASDA-B2 codes
Source
Delta Electronics, ASDA-B2 Standard AC Servo Drive User Manual, Revision May 2018, DELTA_IA-ASDA_B2_UM_EN_20180509, Chapter 9, Troubleshooting (9.1 to 9.3).
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007