MachineryFix

Siemens Servo drive · fault code

SINAMICS V90 F7430: Changeover to open-loop torque controlled operation not possible

F7430 on the Siemens SINAMICS V90 is the “Changeover to open-loop torque controlled operation not possible” fault. A fault triggers the reaction set for it: OFF1 ramps the motor down, OFF2 lets it coast down, OFF3 stops it quickly as an emergency stop, and NONE takes no action. Each fault page gives the reaction and the acknowledgement type.

The speed or position feedback from the encoder is missing or does not agree with what the drive expects.

Code
F7430
Type
Fault (stops the drive)
Drive
Siemens SINAMICS V90, SIMOTICS S-1FL6
Kind of fault
Encoder signal

01 / Causes

What causes F7430

  • In encoderless operation, the converter cannot change over to closed-loop torque control.

02 / Checks

What to check for F7430

In the order Siemens gives them.

  1. 01Do not try to change over to closed-loop torque control.
  2. 02Check the encoder cable connection.

Also in the manual

  • Reaction OFF2: the motor coasts down. Acknowledgement POWER ON: power the drive off and on after removing the cause.

03 / Clearing it

How to clear F7430

  • Remove the cause first. Then acknowledge the fault on the BOP, with the RESET digital input, or in SINAMICS V-ASSISTANT.
  • Each fault has its own acknowledgement type: POWER ON (power the drive off and on after removing the cause), IMMEDIATELY (it clears once the cause is removed), or PULSE INHIBIT (it can only be acknowledged with a pulse inhibit).
  • If the cause is not removed, the fault can come back after five seconds with no button pressed.
  • Alarms acknowledge themselves.

Clear it once. If F7430 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How encoder signal faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check the encoder cable and connectors, and that the screen is earthed at the right end.
  2. 02Check the encoder's supply voltage.
  3. 03Check the encoder settings (type, pulses per revolution) in the drive.

05 / Repair

When F7430 means a repair

A damaged encoder or cable is replaced; a drive encoder input that has failed needs the drive repaired.

If F7430 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Siemens drives, and they arrive knowing what to look for.

06 / Other drives

Encoder signal: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens MICROMASTER 440F0090 Signal loss, encoder · A0590 Alarm, no signals from the speed encoder
Allen-Bradley PowerFlex 525F091 Encoder Loss
ABB ACS355F0023 ENCODER ERR · A2024 ENCODER ERROR
Delta VFD-EPGEr PG feedback signal error
Delta C2000PGF1 PG feedback error · PGF2 PG feedback loss · PGF3 PG feedback stall · PGF4 PG slip error · PGF5 Hardware error of PG card · AboF PG ABZ line off
Delta ASDA-B2AL004 Motor combination error · AL011 Encoder error · AL018 Abnormal signal output · AL024 Encoder initial magnetic field error · AL025 The internal of the encoder is in error · AL026 Unreliable internal data of the encoder
Hitachi WJ200E80 Encoder disconnection
Schneider Electric Altivar ATV320SPF Encoder feedback loss error
Yaskawa V1000dEv Speed Deviation (for Simple V/f with PG) · oS Overspeed (Simple V/f with PG) · PGo PG Disconnect (for Simple V/f with PG)
Yaskawa A1000dEv Speed Deviation · dv1 Z Pulse Fault · dv2 Z Pulse Noise Fault Detection · dv3 Inversion Detection · dv4 Inversion Prevention Detection · oS Overspeed
Yaskawa GA500dEv Speed Deviation · oS Overspeed · PGo Encoder (PG) Feedback Loss
Siemens MICROMASTER 430F0090 Signal loss, encoder · A0590 Alarm, no signals from the speed encoder

07 / More codes

Other SINAMICS V90 codes

Source

Siemens, SINAMICS V90, SIMOTICS S-1FL6 Operating Instructions, 04/2014, 6SL3298-0AV60-0BP0, 11 Diagnostics (11.2 List of faults and alarms).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Siemens and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

F7430 won't clear? Get a technician who knows the SINAMICS V90.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.