MachineryFix

Delta Servo drive · alarm code

ASDA-B2 AL048: Excessive encoder output error

AL048 on the Delta ASDA-B2 is the “Excessive encoder output error” alarm. This alarm switches the servo off, so the motor is no longer driven until the alarm is cleared.

The speed or position feedback from the encoder is missing or does not agree with what the drive expects.

Code
AL048
Type
Alarm (stops the drive)
Drive
Delta ASDA-B2
Kind of fault
Encoder signal

01 / Causes

What causes AL048

  • An encoder error causes abnormal encoder output.
  • The output pulse exceeds the hardware's tolerance.

02 / Checks

What to check for AL048

In the order Delta Electronics gives them.

  1. 01Check the fault records (P4-00 to P4-04) for an encoder alarm (AL011, AL024, AL025 or AL026) at the same time, and if so follow that alarm's corrective actions.
  2. 02Check whether the output pulse frequency, set by P1-76 and P1-46, falls below what the motor speed needs; set P1-76 and P1-46 so it stays above it, using the formula in the manual.

Also in the manual

  • ALM output; servo off. Clears by turning on the alarm reset input (DI.ARST).

03 / Clearing it

How to clear AL048

  • Remove the cause first. Most alarms clear by turning on the alarm reset input, DI.ARST (assigned to DI5 by default).
  • Some alarms clear only after the drive is powered off and on: AL004, AL011, AL024 to AL029, AL031 and AL035. AL003 also needs a power cycle, unless P2-66 bit 2 is set so it clears once the voltage is back to normal.
  • AL013 clears by itself once the emergency stop input (DI.EMGS) is off. AL014 and AL015 clear with DI.ARST, by switching the servo off, or by moving the motor back off the limit.
  • AL099 clears by setting P2-08 to 30, then to 28, and powering the drive off and on. For AL555 and AL880, do nothing to the drive: Delta's instruction is to send it back to the distributor or contact Delta.

Clear it once. If AL048 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How encoder signal faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check the encoder cable and connectors, and that the screen is earthed at the right end.
  2. 02Check the encoder's supply voltage.
  3. 03Check the encoder settings (type, pulses per revolution) in the drive.

05 / Repair

When AL048 means a repair

A damaged encoder or cable is replaced; a drive encoder input that has failed needs the drive repaired.

If AL048 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Delta drives, and they arrive knowing what to look for.

06 / Other drives

Encoder signal: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V90F7412 Commutation angle incorrect (motor model) · F7430 Changeover to open-loop torque controlled operation not possible · F7431 Changeover to encoderless operation not possible · F7453 Position actual value preprocessing error · F7599 Encoder 1: Adjustment not possible · F31100 Zero mark distance error
Siemens MICROMASTER 440F0090 Signal loss, encoder · A0590 Alarm, no signals from the speed encoder
Allen-Bradley PowerFlex 525F091 Encoder Loss
ABB ACS355F0023 ENCODER ERR · A2024 ENCODER ERROR
Delta VFD-EPGEr PG feedback signal error
Delta C2000PGF1 PG feedback error · PGF2 PG feedback loss · PGF3 PG feedback stall · PGF4 PG slip error · PGF5 Hardware error of PG card · AboF PG ABZ line off
Hitachi WJ200E80 Encoder disconnection
Schneider Electric Altivar ATV320SPF Encoder feedback loss error
Yaskawa V1000dEv Speed Deviation (for Simple V/f with PG) · oS Overspeed (Simple V/f with PG) · PGo PG Disconnect (for Simple V/f with PG)
Yaskawa A1000dEv Speed Deviation · dv1 Z Pulse Fault · dv2 Z Pulse Noise Fault Detection · dv3 Inversion Detection · dv4 Inversion Prevention Detection · oS Overspeed
Yaskawa GA500dEv Speed Deviation · oS Overspeed · PGo Encoder (PG) Feedback Loss
Siemens MICROMASTER 430F0090 Signal loss, encoder · A0590 Alarm, no signals from the speed encoder

07 / More codes

Other ASDA-B2 codes

Source

Delta Electronics, ASDA-B2 Standard AC Servo Drive User Manual, Revision May 2018, DELTA_IA-ASDA_B2_UM_EN_20180509, Chapter 9, Troubleshooting (9.1 to 9.3).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

AL048 won't clear? Get a technician who knows the ASDA-B2.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.