F0023 on the ABB ACS355 is the “ENCODER ERR” fault. A fault stops the drive and lights its red LED. The drive will not run again until the fault is reset.
The speed or position feedback from the encoder is missing or does not agree with what the drive expects.
- Code
- F0023
- Type
- Fault (stops the drive)
- Drive
- ABB ACS355
- Kind of fault
- Encoder signal
01 / Causes
What causes F0023
- A communication fault between the pulse encoder and the pulse encoder interface module, or between the module and the drive.
02 / Checks
What to check for F0023
In the order ABB gives them.
- 01Check the pulse encoder and its wiring.
- 02Check the pulse encoder interface module and its wiring.
- 03Check the settings in parameter group 50 ENCODER.
Also in the manual
- Over a fieldbus, the drive reports this fault as code 7301.
- ABB lists this as a programmable fault function: parameters 5003 decide whether the condition is reported and how the drive reacts.
03 / Clearing it
How to clear F0023
- Reset with the RESET key on the control panel, through a digital input or fieldbus, or by switching the supply off for a while. Parameter 1604 FAULT RESET SEL chooses the reset source. Once the cause is gone, the motor can be restarted.
- If the red LED on the drive is blinking rather than steady, the fault can only be reset by switching the drive's power off.
- Parameters 0401 LAST FAULT, 0412 PREVIOUS FAULT 1 and 0413 PREVIOUS FAULT 2 hold the three most recent faults, and 0404 to 0409 show the drive's operating data at the moment of the latest one.
Clear it once. If F0023 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How encoder signal faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check the encoder cable and connectors, and that the screen is earthed at the right end.
- 02Check the encoder's supply voltage.
- 03Check the encoder settings (type, pulses per revolution) in the drive.
05 / Repair
When F0023 means a repair
A damaged encoder or cable is replaced; a drive encoder input that has failed needs the drive repaired.
If F0023 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on ABB drives, and they arrive knowing what to look for.
06 / Other drives
Encoder signal: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V90 | F7412 Commutation angle incorrect (motor model) · F7430 Changeover to open-loop torque controlled operation not possible · F7431 Changeover to encoderless operation not possible · F7453 Position actual value preprocessing error · F7599 Encoder 1: Adjustment not possible · F31100 Zero mark distance error |
| Siemens MICROMASTER 440 | F0090 Signal loss, encoder · A0590 Alarm, no signals from the speed encoder |
| Allen-Bradley PowerFlex 525 | F091 Encoder Loss |
| Delta VFD-E | PGEr PG feedback signal error |
| Delta C2000 | PGF1 PG feedback error · PGF2 PG feedback loss · PGF3 PG feedback stall · PGF4 PG slip error · PGF5 Hardware error of PG card · AboF PG ABZ line off |
| Delta ASDA-B2 | AL004 Motor combination error · AL011 Encoder error · AL018 Abnormal signal output · AL024 Encoder initial magnetic field error · AL025 The internal of the encoder is in error · AL026 Unreliable internal data of the encoder |
| Hitachi WJ200 | E80 Encoder disconnection |
| Schneider Electric Altivar ATV320 | SPF Encoder feedback loss error |
| Yaskawa V1000 | dEv Speed Deviation (for Simple V/f with PG) · oS Overspeed (Simple V/f with PG) · PGo PG Disconnect (for Simple V/f with PG) |
| Yaskawa A1000 | dEv Speed Deviation · dv1 Z Pulse Fault · dv2 Z Pulse Noise Fault Detection · dv3 Inversion Detection · dv4 Inversion Prevention Detection · oS Overspeed |
| Yaskawa GA500 | dEv Speed Deviation · oS Overspeed · PGo Encoder (PG) Feedback Loss |
| Siemens MICROMASTER 430 | F0090 Signal loss, encoder · A0590 Alarm, no signals from the speed encoder |
07 / More codes
Other ACS355 codes
Source
ABB, ACS355 user's manual, Rev E, effective 2 November 2020, 3AUA0000066143, Fault tracing.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of ABB and is not its authorised service partner.