dEv on the Yaskawa GA500 is the “Speed Deviation” fault. A fault shuts off the drive's output and the motor coasts to a stop (some faults let you choose the stopping method). ALM/ERR stays lit, a terminal set to H2-01 to H2-03 = E activates, and the drive will not run until the fault is reset.
The speed or position feedback from the encoder is missing or does not agree with what the drive expects.
- Code
- dEv
- Type
- Fault (stops the drive)
- Drive
- Yaskawa GA500
- Kind of fault
- Encoder signal
01 / Causes
What causes dEv
- The load is too heavy or locked, or the holding brake is stopping the motor.
- Acceleration and deceleration times too short, or the dEv detection settings wrong.
02 / Checks
What to check for dEv
In the order Yaskawa gives them.
- 01Reduce the load, check the machine, and release the holding brake.
- 02Lengthen C1-01 to C1-08.
- 03Adjust F1-10 (detection level) and F1-11 (delay time).
Also in the manual
- Detected when speed feedback and reference differ by more than F1-10 for longer than F1-11. F1-04 sets the stopping method.
- The GA500 can also show this code as a minor fault or alarm: ALM/ERR flashes instead of staying lit, and the drive keeps running unless set to stop.
03 / Clearing it
How to clear dEv
- Remove the cause, then reset in one of three ways: the reset key on the keypad while the code is shown, a multi-function input set to H1-xx = 14 (terminal S4 by default), or switching off the main circuit power and switching it back on once the keypad display has gone out.
- A fault will not reset while a run command is active from the terminals or a communication option; the keypad shows CrST until the run command is removed.
- oL1 resets only once monitor U4-16 (Motor oL1 Level) is below 100.
Clear it once. If dEv comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How encoder signal faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Check the encoder cable and connectors, and that the screen is earthed at the right end.
- 02Check the encoder's supply voltage.
- 03Check the encoder settings (type, pulses per revolution) in the drive.
05 / Repair
When dEv means a repair
A damaged encoder or cable is replaced; a drive encoder input that has failed needs the drive repaired.
If dEv keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.
06 / Other drives
Encoder signal: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V90 | F7412 Commutation angle incorrect (motor model) · F7430 Changeover to open-loop torque controlled operation not possible · F7431 Changeover to encoderless operation not possible · F7453 Position actual value preprocessing error · F7599 Encoder 1: Adjustment not possible · F31100 Zero mark distance error |
| Siemens MICROMASTER 440 | F0090 Signal loss, encoder · A0590 Alarm, no signals from the speed encoder |
| Allen-Bradley PowerFlex 525 | F091 Encoder Loss |
| ABB ACS355 | F0023 ENCODER ERR · A2024 ENCODER ERROR |
| Delta VFD-E | PGEr PG feedback signal error |
| Delta C2000 | PGF1 PG feedback error · PGF2 PG feedback loss · PGF3 PG feedback stall · PGF4 PG slip error · PGF5 Hardware error of PG card · AboF PG ABZ line off |
| Delta ASDA-B2 | AL004 Motor combination error · AL011 Encoder error · AL018 Abnormal signal output · AL024 Encoder initial magnetic field error · AL025 The internal of the encoder is in error · AL026 Unreliable internal data of the encoder |
| Hitachi WJ200 | E80 Encoder disconnection |
| Schneider Electric Altivar ATV320 | SPF Encoder feedback loss error |
| Yaskawa V1000 | dEv Speed Deviation (for Simple V/f with PG) · oS Overspeed (Simple V/f with PG) · PGo PG Disconnect (for Simple V/f with PG) |
| Yaskawa A1000 | dEv Speed Deviation · dv1 Z Pulse Fault · dv2 Z Pulse Noise Fault Detection · dv3 Inversion Detection · dv4 Inversion Prevention Detection · oS Overspeed |
| Siemens MICROMASTER 430 | F0090 Signal loss, encoder · A0590 Alarm, no signals from the speed encoder |
07 / More codes
Other GA500 codes
Source
Yaskawa, GA500 Drive Technical Reference, C, SIEP C710617 52, 7 Troubleshooting (7.4 to 7.7, 7.9).
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007