Schneider Electric AC drive (VFD) · fault code

Altivar ATV320 SPF: Encoder feedback loss error

SPF on the Schneider Electric Altivar ATV320 is the “Encoder feedback loss error” fault. A detected error stops the drive until it is cleared, in the way the manual gives for that code.

The speed or position feedback from the encoder is missing or does not agree with what the drive expects.

Code
SPF
Type
Fault (stops the drive)
Drive
Schneider Electric Altivar ATV320
Kind of fault
Encoder signal

01 / Causes

What causes SPF

  • The signal on the pulse input is missing, when that input measures speed.
  • The encoder feedback signal is missing.

02 / Checks

What to check for SPF

In the order Schneider Electric gives them.

  1. 01Check the wiring of the input cable and the detector used.
  2. 02Check the encoder's configuration parameters.
  3. 03Check the wiring between the encoder and the drive.
  4. 04Check the encoder.

Also in the manual

  • Can be cleared by Auto Fault Reset (ATR), or with the Fault Reset Assign (RSF) input or control bit, after the cause is removed. Switching the drive off and on also clears it.

03 / Clearing it

How to clear SPF

  • Remove the cause first. A resettable error can then be cleared by switching the drive off until the display goes out completely and back on, automatically by the Auto Fault Reset (ATR) function, through an input or control bit assigned to Fault reset (RST), or with the STOP/RESET key on the graphic display terminal when it is the active command channel.
  • Some codes need a power reset (ANF, ASF, BLF, BRF, CRF1, EEF1, EEF2, FCF1, HDF, ILF, the INF codes, SAFF, SOF, SPF); ASF, BRF, SOF, SPF and TNF can also be cleared remotely with Fault Reset Assign (RSF).
  • For an error that cannot be reset, Schneider's steps are: disconnect all power, including external control power; lock the disconnects open; wait 15 minutes for the DC bus capacitors to discharge; check the DC bus between PA/+ and PC/- is below 42 V DC; find and fix the cause; then restore power to confirm.

Clear it once. If SPF comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How encoder signal faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check the encoder cable and connectors, and that the screen is earthed at the right end.
  2. 02Check the encoder's supply voltage.
  3. 03Check the encoder settings (type, pulses per revolution) in the drive.

05 / Repair

When SPF means a repair

A damaged encoder or cable is replaced; a drive encoder input that has failed needs the drive repaired.

If SPF keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Schneider Electric drives, and they arrive knowing what to look for.

06 / Other drives

Encoder signal: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V90F7412 Commutation angle incorrect (motor model) · F7430 Changeover to open-loop torque controlled operation not possible · F7431 Changeover to encoderless operation not possible · F7453 Position actual value preprocessing error · F7599 Encoder 1: Adjustment not possible · F31100 Zero mark distance error
Siemens MICROMASTER 440F0090 Signal loss, encoder · A0590 Alarm, no signals from the speed encoder
Allen-Bradley PowerFlex 525F091 Encoder Loss
ABB ACS355F0023 ENCODER ERR · A2024 ENCODER ERROR
Delta VFD-EPGEr PG feedback signal error
Delta C2000PGF1 PG feedback error · PGF2 PG feedback loss · PGF3 PG feedback stall · PGF4 PG slip error · PGF5 Hardware error of PG card · AboF PG ABZ line off
Delta ASDA-B2AL004 Motor combination error · AL011 Encoder error · AL018 Abnormal signal output · AL024 Encoder initial magnetic field error · AL025 The internal of the encoder is in error · AL026 Unreliable internal data of the encoder
Hitachi WJ200E80 Encoder disconnection
Yaskawa V1000dEv Speed Deviation (for Simple V/f with PG) · oS Overspeed (Simple V/f with PG) · PGo PG Disconnect (for Simple V/f with PG)
Yaskawa A1000dEv Speed Deviation · dv1 Z Pulse Fault · dv2 Z Pulse Noise Fault Detection · dv3 Inversion Detection · dv4 Inversion Prevention Detection · oS Overspeed
Yaskawa GA500dEv Speed Deviation · oS Overspeed · PGo Encoder (PG) Feedback Loss
Siemens MICROMASTER 430F0090 Signal loss, encoder · A0590 Alarm, no signals from the speed encoder

07 / More codes

Other Altivar ATV320 codes

Source

Schneider Electric, Altivar Machine ATV320 Programming Manual, 04/2025, NVE41295.06, Diagnostics and Troubleshooting.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Schneider Electric and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

SPF won't clear? Get a technician who knows the Altivar ATV320.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.