GA500 oS: Overspeed

oS on the Yaskawa GA500 is the “Overspeed” fault. A fault shuts off the drive's output and the motor coasts to a stop (some faults let you choose the stopping method). ALM/ERR stays lit, a terminal set to H2-01 to H2-03 = E activates, and the drive will not run until the fault is reset.

The speed or position feedback from the encoder is missing or does not agree with what the drive expects.

Code
oS
Type
Fault (stops the drive)
Drive
Yaskawa GA500
Kind of fault
Encoder signal

01 / Causes

What causes oS

  • Speed overshoot, the wrong pulse train scaling, or the oS detection level set wrongly.
  • In PM control with n8-57 = 1, a high frequency injection gain that is too high.

02 / Checks

What to check for oS

In the order Yaskawa gives them.

  1. 01Lower C5-01 and raise C5-02; adjust the pulse train input with H6-02 to H6-05.
  2. 02Set H6-02 to the pulse frequency at 100% reference (maximum motor speed).
  3. 03Adjust F1-08 (level) and F1-09 (delay time).
  4. 04If the trip happens at start or below 10% speed with n8-57 = 1 (HFI Overlap) in a PM control method, the high frequency injection gain is too high: set the E5 parameters correctly or do Rotational Auto-Tuning, and lower n8-41 in steps of 0.5 (keep n8-41 above 0.0 for IPM motors).

Also in the manual

  • F1-03 sets the stopping method.
  • The GA500 can also show this code as a minor fault or alarm: ALM/ERR flashes instead of staying lit, and the drive keeps running unless set to stop.

03 / Clearing it

How to clear oS

  • Remove the cause, then reset in one of three ways: the reset key on the keypad while the code is shown, a multi-function input set to H1-xx = 14 (terminal S4 by default), or switching off the main circuit power and switching it back on once the keypad display has gone out.
  • A fault will not reset while a run command is active from the terminals or a communication option; the keypad shows CrST until the run command is removed.
  • oL1 resets only once monitor U4-16 (Motor oL1 Level) is below 100.

Clear it once. If oS comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How encoder signal faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Check the encoder cable and connectors, and that the screen is earthed at the right end.
  2. 02Check the encoder's supply voltage.
  3. 03Check the encoder settings (type, pulses per revolution) in the drive.

05 / Repair

When oS means a repair

A damaged encoder or cable is replaced; a drive encoder input that has failed needs the drive repaired.

If oS keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.

06 / Other drives

Encoder signal: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS V90F7412 Commutation angle incorrect (motor model) · F7430 Changeover to open-loop torque controlled operation not possible · F7431 Changeover to encoderless operation not possible · F7453 Position actual value preprocessing error · F7599 Encoder 1: Adjustment not possible · F31100 Zero mark distance error
Siemens MICROMASTER 440F0090 Signal loss, encoder · A0590 Alarm, no signals from the speed encoder
Allen-Bradley PowerFlex 525F091 Encoder Loss
ABB ACS355F0023 ENCODER ERR · A2024 ENCODER ERROR
Delta VFD-EPGEr PG feedback signal error
Delta C2000PGF1 PG feedback error · PGF2 PG feedback loss · PGF3 PG feedback stall · PGF4 PG slip error · PGF5 Hardware error of PG card · AboF PG ABZ line off
Delta ASDA-B2AL004 Motor combination error · AL011 Encoder error · AL018 Abnormal signal output · AL024 Encoder initial magnetic field error · AL025 The internal of the encoder is in error · AL026 Unreliable internal data of the encoder
Hitachi WJ200E80 Encoder disconnection
Schneider Electric Altivar ATV320SPF Encoder feedback loss error
Yaskawa V1000dEv Speed Deviation (for Simple V/f with PG) · oS Overspeed (Simple V/f with PG) · PGo PG Disconnect (for Simple V/f with PG)
Yaskawa A1000dEv Speed Deviation · dv1 Z Pulse Fault · dv2 Z Pulse Noise Fault Detection · dv3 Inversion Detection · dv4 Inversion Prevention Detection · oS Overspeed
Siemens MICROMASTER 430F0090 Signal loss, encoder · A0590 Alarm, no signals from the speed encoder

07 / More codes

Other GA500 codes

Source

Yaskawa, GA500 Drive Technical Reference, C, SIEP C710617 52, 7 Troubleshooting (7.4 to 7.7, 7.9).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

oS won't clear? Get a technician who knows the GA500.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.