TRAP on the Delta C2000 is the “CPU error 0” fault. A fault stops the drive's output. On over-current and over-voltage faults the drive closes its output gate at once and the motor coasts to a stop.
The drive's own electronics reported a problem: a self-test, a processor, an internal link or the power module's identification. There is nothing in the machine to fix.
- Code
- TRAP
- Type
- Fault (stops the drive)
- Drive
- Delta C2000
- Kind of fault
- Internal drive fault
01 / Causes
What causes TRAP
- Hardware interference.
- A hardware failure.
- The CPU is stuck in an endless loop.
02 / Checks
What to check for TRAP
In the order Delta Electronics gives them.
- 01Check the control-circuit wiring and the main-circuit wiring and grounding, to keep interference out. If it is still there, Delta's instruction is to return the drive to the factory for repair.
- 02Delta's instruction is to return the drive to the factory for repair.
- 03Switch the power off and on. If it is still there, Delta's instruction is to return the drive to the factory for repair.
Also in the manual
- Fault ID 93. A CPU crash. Cannot be reset: switch the power off.
03 / Clearing it
How to clear TRAP
- Remove the cause first. Then press STOP/RESET on the keypad, or switch on a multi-function input set to 5 (Reset).
- Most faults can be reset 5 seconds after the fault has cleared. Over-voltage faults reset only once the DC bus is below 90% of the trip level, and overheating faults only once the temperature is 10°C below it.
- Some faults can only be cleared by switching the power off: the current detection and hardware protection faults (cd1 to cd3, Hd0 to Hd3), the watchdog (WDTT), STO Loss (STL1 to STL3) and the CPU error (TRAP).
- After resetting, if the keypad returns to its main page and shows no fault after ESC, the fault is cleared.
Clear it once. If TRAP comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How internal drive fault faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Power-cycle the drive and note whether the fault returns.
- 02Check for electrical noise: screened cables, earthing and an EMC filter where the manual calls for one.
- 03Note the fault value the drive shows with the code; the manufacturer uses it to narrow the cause.
05 / Repair
When TRAP means a repair
If the fault survives a power cycle, the drive needs a bench repair or replacement.
If TRAP keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Delta drives, and they arrive knowing what to look for.
06 / Other drives
Internal drive fault: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS V20 | F52 Inverter software fault · F60 Asic timeout · F100 Watchdog reset · F101 Stack overflow · F200 Script error · F350 Configuration vector for the inverter failed |
| Siemens SINAMICS G120 | F01000 Software error in the CU · F01001 Floating point exception · F01015 Software error in the CU · F01018 Power-up aborted more than once · F01054 System limit exceeded · F01205 CU: Time slice overflow |
| Siemens SINAMICS V90 | F1000 Internal software error · F1001 FloatingPoint exception · F1002 Internal software error · F1003 Acknowledgement delay when accessing the memory · F1015 Internal software error · F1018 Booting has been interrupted several times |
| Siemens MICROMASTER 440 | F0040 Fault, for automatic calibration · F0052 Power stack fault · F0053 I/O EEPROM fault · F0054 Incorrect I/O module · F0060 Asic time slice overflow · F0101 Stack overflow |
| Allen-Bradley PowerFlex 525 | F070 Power Unit · F105 C Connect Err · F106 Incompat C-P · F107 Replaced C-P · F109 Mismatch C-P · F110 Keypad Membrane |
| ABB ACS355 | F0021 CURR MEAS · F0027 CONFIG FILE · F0036 INCOMPATIBLE SW · F0101 SERF CORRUPT · F0103 SERF MACRO · F0201 DSP T1 OVERLOAD |
| Delta VFD-E | HPF1 CC, OC hardware protection failure · HPF2 OV hardware protection failure · HPF3 GFF hardware protection failure · HPF4 OC hardware protection failure · codE Software protection failure · cF3.0 U-phase error |
| Delta ASDA-B2 | AL012 Adjustment error · AL555 System failure · AL880 System failure |
| Hitachi WJ200 | E10 Current detection error · E11 CPU error · E22 CPU communication error · E25 Main circuit error · E30 Driver error · E63 Option error |
| Schneider Electric Altivar ATV320 | CRF1 Precharge capacitor error · ILF Internal link error · INF1 Internal error 1 (Rating) · INF2 Internal error 2 (Soft) · INF3 Internal error 3 (Intern Comm) · INF4 Internal error 4 (Manufacturing) |
| INVT Goodrive20 (GD20) | ItE Current detection fault |
| Yaskawa V1000 | CoF Current Offset Fault · CPF02 A/D Conversion Error · CPF03 PWM Data Error · CPF07 Terminal Board Communications Error · CPF08 EEPROM Serial Communication Fault · CPF11 RAM Fault |
| Yaskawa A1000 | CoF Current Offset Fault · CPF02 A/D Conversion Error · CPF03 Control Board Connection Error · CPF07 Terminal Board Connection Error · CPF08 Terminal Board Connection Error · CPF11 RAM Fault |
| Yaskawa GA500 | bAT Keypad Battery Low Voltage · CoF Current Offset Fault · CPF00 Control Circuit Error · CPF01 Control Circuit Error · CPF02 Control Circuit Error · CPF03 Control Circuit Error |
| Siemens MICROMASTER 420 | F0052 Power stack fault · F0060 Asic time slice overflow · F0101 Stack overflow · F0450 Failure BIST tests · A0600 RTOS data loss alarm |
| Siemens MICROMASTER 430 | F0052 Power stack fault · F0054 Incorrect I/O module · F0060 Asic time slice overflow · F0101 Stack overflow · F0450 Failure BIST tests · A0522 Read I2C, time exceeded |
| Siemens SINAMICS G110 | F0052 Power stack fault · F0060 Asic timeout · F0100 Watchdog reset · F0101 Stack overflow |
| INVT Goodrive200A (GD200A) | ItE Current detection fault |
| Mitsubishi Electric FR-D700 | E.CPU CPU fault · E.IOH Inrush current limit circuit fault |
| Danfoss VLT Micro Drive FC 51 | Alarm 38 Internal fault · Alarm 46 Gate drive voltage fault · Alarm 47 Control voltage fault |
07 / More codes
Other C2000 codes
Source
Delta Electronics, C2000 Series User Manual, Issued edition 01, firmware V2.05 (2019-02-13), DELTA_IA-MDS_VFD-C2000_UM_EN_20190213, Chapter 14, Fault Codes and Descriptions.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007