Goodrive20 (GD20) OUt3: Inverter unit W phase protection

OUt3 on the INVT Goodrive20 (GD20) is the “Inverter unit W phase protection” fault. A fault trips the drive and lights the TRIP indicator; the drive stays stopped until the fault is reset.

The drive detected a short between two output phases. It stops at once, because a phase-to-phase short drives current far beyond what the output stage can carry.

Code
OUt3
Type
Fault (stops the drive)
Drive
INVT Goodrive20 (GD20)
Kind of fault
Output short circuit

01 / Causes

What causes OUt3

  • Acceleration too fast.
  • A fault in the IGBT module.
  • False trips caused by interference.
  • A poor connection in the drive wiring.
  • Improper grounding.

02 / Checks

What to check for OUt3

In the order INVT gives them.

  1. 01Lengthen the acceleration time.
  2. 02Replace the power unit.
  3. 03Check the drive wiring.
  4. 04Check external equipment and remove sources of interference.

Also in the manual

  • Over communication this fault reads as type 3.

03 / Clearing it

How to clear OUt3

  • Remove the cause, then reset with the keypad's STOP/RST key, through a digital input, or by switching the power off and on. Once the fault is cleared the motor can be restarted.
  • INVT's order of work: check the keypad is working; read the fault records in group P07 to see the drive's state when the fault happened; follow the table for that code; fix the cause; then reset and run.

Clear it once. If OUt3 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How output short circuit faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Isolate and discharge, then disconnect the motor cable at the drive terminals.
  2. 02Measure phase to phase on the cable and on the motor separately, and insulation-test between phases.
  3. 03Inspect the motor terminal box for loose links, tracking or a burnt terminal board.
  4. 04Check that nothing between drive and motor (a contactor, isolator or junction box) has failed or been miswired.

05 / Repair

When OUt3 means a repair

If the cable and motor are clear and the fault stays with nothing connected to the output, the drive's output stage has failed.

If OUt3 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on INVT drives, and they arrive knowing what to look for.

06 / Other drives

Output short circuit: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS G120F07807 Short-circuit detected
Allen-Bradley PowerFlex 525F041 Phase UV Short · F042 Phase UW Short · F043 Phase VW Short
ABB ACS355F0004 SHORT CIRC
Delta C2000occ IGBT short circuit between upper bridge and lower bridge
Delta ASDA-B2AL083 Servo drive outputs excessive current
Schneider Electric Altivar ATV320HDF IGBT desaturation error · SCF1 Motor short circuit error · SCF5 Motor short circuit error
Yaskawa V1000SC IGBT Short Circuit
Yaskawa A1000SC Output Short Circuit or IGBT Fault
Yaskawa GA500SC Short Circuit/IGBT Failure
Siemens MICROMASTER 430F0022 Hardware monitoring active
INVT Goodrive200A (GD200A)OUt1 Inverter unit U-phase protection · OUt2 Inverter unit V-phase protection · OUt3 Inverter unit W-phase protection
Danfoss VLT Micro Drive FC 51Alarm 16 Short circuit

07 / More codes

Other Goodrive20 (GD20) codes

Source

INVT, Goodrive20 Series VFD Manual, Version V2.1 (2025), Chapter 6, Fault tracking (6.2.3 VFD faults and solutions).

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of INVT and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

OUt3 won't clear? Get a technician who knows the Goodrive20 (GD20).

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.