MachineryFix

Schneider Electric AC drive (VFD) · fault code

Altivar ATV320 SCF1: Motor short circuit error

SCF1 on the Schneider Electric Altivar ATV320 is the “Motor short circuit error” fault. A detected error stops the drive until it is cleared, in the way the manual gives for that code.

The drive detected a short between two output phases. It stops at once, because a phase-to-phase short drives current far beyond what the output stage can carry.

Code
SCF1
Type
Fault (stops the drive)
Drive
Schneider Electric Altivar ATV320
Kind of fault
Output short circuit

01 / Causes

What causes SCF1

  • A short circuit or ground fault at the drive output.

02 / Checks

What to check for SCF1

In the order Schneider Electric gives them.

  1. 01Check the cables between the drive and the motor, and the motor's insulation.
  2. 02Adjust the switching frequency.
  3. 03Connect chokes in series with the motor.
  4. 04Check the speed loop and brake settings.
  5. 05Increase the time to restart (TTR).

Also in the manual

  • With Extended Fault Reset (HRFC) set to No, it needs a power reset; set to Yes, it can be cleared with the Fault Reset Assign (RSF) input or control bit after the cause is removed.

03 / Clearing it

How to clear SCF1

  • Remove the cause first. A resettable error can then be cleared by switching the drive off until the display goes out completely and back on, automatically by the Auto Fault Reset (ATR) function, through an input or control bit assigned to Fault reset (RST), or with the STOP/RESET key on the graphic display terminal when it is the active command channel.
  • Some codes need a power reset (ANF, ASF, BLF, BRF, CRF1, EEF1, EEF2, FCF1, HDF, ILF, the INF codes, SAFF, SOF, SPF); ASF, BRF, SOF, SPF and TNF can also be cleared remotely with Fault Reset Assign (RSF).
  • For an error that cannot be reset, Schneider's steps are: disconnect all power, including external control power; lock the disconnects open; wait 15 minutes for the DC bus capacitors to discharge; check the DC bus between PA/+ and PC/- is below 42 V DC; find and fix the cause; then restore power to confirm.

Clear it once. If SCF1 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How output short circuit faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Isolate and discharge, then disconnect the motor cable at the drive terminals.
  2. 02Measure phase to phase on the cable and on the motor separately, and insulation-test between phases.
  3. 03Inspect the motor terminal box for loose links, tracking or a burnt terminal board.
  4. 04Check that nothing between drive and motor (a contactor, isolator or junction box) has failed or been miswired.

05 / Repair

When SCF1 means a repair

If the cable and motor are clear and the fault stays with nothing connected to the output, the drive's output stage has failed.

If SCF1 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Schneider Electric drives, and they arrive knowing what to look for.

06 / Other drives

Output short circuit: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS G120F07807 Short-circuit detected
Allen-Bradley PowerFlex 525F041 Phase UV Short · F042 Phase UW Short · F043 Phase VW Short
ABB ACS355F0004 SHORT CIRC
Delta C2000occ IGBT short circuit between upper bridge and lower bridge
Delta ASDA-B2AL083 Servo drive outputs excessive current
INVT Goodrive20 (GD20)OUt1 Inverter unit U phase protection · OUt2 Inverter unit V phase protection · OUt3 Inverter unit W phase protection
Yaskawa V1000SC IGBT Short Circuit
Yaskawa A1000SC Output Short Circuit or IGBT Fault
Yaskawa GA500SC Short Circuit/IGBT Failure
Siemens MICROMASTER 430F0022 Hardware monitoring active
INVT Goodrive200A (GD200A)OUt1 Inverter unit U-phase protection · OUt2 Inverter unit V-phase protection · OUt3 Inverter unit W-phase protection
Danfoss VLT Micro Drive FC 51Alarm 16 Short circuit

07 / More codes

Other Altivar ATV320 codes

Source

Schneider Electric, Altivar Machine ATV320 Programming Manual, 04/2025, NVE41295.06, Diagnostics and Troubleshooting.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Schneider Electric and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007

SCF1 won't clear? Get a technician who knows the Altivar ATV320.

Send the code and what the machine was doing when it tripped. We'll match a technician who works on that drive.