SCF1 on the Schneider Electric Altivar ATV320 is the “Motor short circuit error” fault. A detected error stops the drive until it is cleared, in the way the manual gives for that code.
The drive detected a short between two output phases. It stops at once, because a phase-to-phase short drives current far beyond what the output stage can carry.
- Code
- SCF1
- Type
- Fault (stops the drive)
- Drive
- Schneider Electric Altivar ATV320
- Kind of fault
- Output short circuit
01 / Causes
What causes SCF1
- A short circuit or ground fault at the drive output.
02 / Checks
What to check for SCF1
In the order Schneider Electric gives them.
- 01Check the cables between the drive and the motor, and the motor's insulation.
- 02Adjust the switching frequency.
- 03Connect chokes in series with the motor.
- 04Check the speed loop and brake settings.
- 05Increase the time to restart (TTR).
Also in the manual
- With Extended Fault Reset (HRFC) set to No, it needs a power reset; set to Yes, it can be cleared with the Fault Reset Assign (RSF) input or control bit after the cause is removed.
03 / Clearing it
How to clear SCF1
- Remove the cause first. A resettable error can then be cleared by switching the drive off until the display goes out completely and back on, automatically by the Auto Fault Reset (ATR) function, through an input or control bit assigned to Fault reset (RST), or with the STOP/RESET key on the graphic display terminal when it is the active command channel.
- Some codes need a power reset (ANF, ASF, BLF, BRF, CRF1, EEF1, EEF2, FCF1, HDF, ILF, the INF codes, SAFF, SOF, SPF); ASF, BRF, SOF, SPF and TNF can also be cleared remotely with Fault Reset Assign (RSF).
- For an error that cannot be reset, Schneider's steps are: disconnect all power, including external control power; lock the disconnects open; wait 15 minutes for the DC bus capacitors to discharge; check the DC bus between PA/+ and PC/- is below 42 V DC; find and fix the cause; then restore power to confirm.
Clear it once. If SCF1 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How output short circuit faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Isolate and discharge, then disconnect the motor cable at the drive terminals.
- 02Measure phase to phase on the cable and on the motor separately, and insulation-test between phases.
- 03Inspect the motor terminal box for loose links, tracking or a burnt terminal board.
- 04Check that nothing between drive and motor (a contactor, isolator or junction box) has failed or been miswired.
05 / Repair
When SCF1 means a repair
If the cable and motor are clear and the fault stays with nothing connected to the output, the drive's output stage has failed.
If SCF1 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Schneider Electric drives, and they arrive knowing what to look for.
06 / Other drives
Output short circuit: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS G120 | F07807 Short-circuit detected |
| Allen-Bradley PowerFlex 525 | F041 Phase UV Short · F042 Phase UW Short · F043 Phase VW Short |
| ABB ACS355 | F0004 SHORT CIRC |
| Delta C2000 | occ IGBT short circuit between upper bridge and lower bridge |
| Delta ASDA-B2 | AL083 Servo drive outputs excessive current |
| INVT Goodrive20 (GD20) | OUt1 Inverter unit U phase protection · OUt2 Inverter unit V phase protection · OUt3 Inverter unit W phase protection |
| Yaskawa V1000 | SC IGBT Short Circuit |
| Yaskawa A1000 | SC Output Short Circuit or IGBT Fault |
| Yaskawa GA500 | SC Short Circuit/IGBT Failure |
| Siemens MICROMASTER 430 | F0022 Hardware monitoring active |
| INVT Goodrive200A (GD200A) | OUt1 Inverter unit U-phase protection · OUt2 Inverter unit V-phase protection · OUt3 Inverter unit W-phase protection |
| Danfoss VLT Micro Drive FC 51 | Alarm 16 Short circuit |
07 / More codes
Other Altivar ATV320 codes
Source
Schneider Electric, Altivar Machine ATV320 Programming Manual, 04/2025, NVE41295.06, Diagnostics and Troubleshooting.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Schneider Electric and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007