SC on the Yaskawa GA500 is the “Short Circuit/IGBT Failure” fault. A fault shuts off the drive's output and the motor coasts to a stop (some faults let you choose the stopping method). ALM/ERR stays lit, a terminal set to H2-01 to H2-03 = E activates, and the drive will not run until the fault is reset.
The drive detected a short between two output phases. It stops at once, because a phase-to-phase short drives current far beyond what the output stage can carry.
- Code
- SC
- Type
- Fault (stops the drive)
- Drive
- Yaskawa GA500
- Kind of fault
- Output short circuit
01 / Causes
What causes SC
- Motor insulation damaged by overheating, the motor cable shorting to ground, or a short or ground fault that damaged the output transistor.
- In OLV/PM or AOLV/PM, the output current went above L8-27 (Overcurrent Detection Gain).
02 / Checks
What to check for SC
In the order Yaskawa gives them.
- 01Measure the motor insulation resistance, and replace the motor if it conducts or the insulation is unserviceable.
- 02Examine the motor cable for damage and repair short circuits; measure the resistance between the motor cable and the ground terminal, and replace the cable if it conducts.
- 03Check for a short circuit between terminal B1 and U/T1, V/T2, W/T3, and between the - terminal and U/T1, V/T2, W/T3; if there is one, contact Yaskawa.
- 04Set L8-27 correctly.
03 / Clearing it
How to clear SC
- Remove the cause, then reset in one of three ways: the reset key on the keypad while the code is shown, a multi-function input set to H1-xx = 14 (terminal S4 by default), or switching off the main circuit power and switching it back on once the keypad display has gone out.
- A fault will not reset while a run command is active from the terminals or a communication option; the keypad shows CrST until the run command is removed.
- oL1 resets only once monitor U4-16 (Motor oL1 Level) is below 100.
Clear it once. If SC comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How output short circuit faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Isolate and discharge, then disconnect the motor cable at the drive terminals.
- 02Measure phase to phase on the cable and on the motor separately, and insulation-test between phases.
- 03Inspect the motor terminal box for loose links, tracking or a burnt terminal board.
- 04Check that nothing between drive and motor (a contactor, isolator or junction box) has failed or been miswired.
05 / Repair
When SC means a repair
If the cable and motor are clear and the fault stays with nothing connected to the output, the drive's output stage has failed.
If SC keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Yaskawa drives, and they arrive knowing what to look for.
06 / Other drives
Output short circuit: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS G120 | F07807 Short-circuit detected |
| Allen-Bradley PowerFlex 525 | F041 Phase UV Short · F042 Phase UW Short · F043 Phase VW Short |
| ABB ACS355 | F0004 SHORT CIRC |
| Delta C2000 | occ IGBT short circuit between upper bridge and lower bridge |
| Delta ASDA-B2 | AL083 Servo drive outputs excessive current |
| Schneider Electric Altivar ATV320 | HDF IGBT desaturation error · SCF1 Motor short circuit error · SCF5 Motor short circuit error |
| INVT Goodrive20 (GD20) | OUt1 Inverter unit U phase protection · OUt2 Inverter unit V phase protection · OUt3 Inverter unit W phase protection |
| Yaskawa V1000 | SC IGBT Short Circuit |
| Yaskawa A1000 | SC Output Short Circuit or IGBT Fault |
| Siemens MICROMASTER 430 | F0022 Hardware monitoring active |
| INVT Goodrive200A (GD200A) | OUt1 Inverter unit U-phase protection · OUt2 Inverter unit V-phase protection · OUt3 Inverter unit W-phase protection |
| Danfoss VLT Micro Drive FC 51 | Alarm 16 Short circuit |
07 / More codes
Other GA500 codes
Source
Yaskawa, GA500 Drive Technical Reference, C, SIEP C710617 52, 7 Troubleshooting (7.4 to 7.7, 7.9).
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Yaskawa and is not its authorised service partner.
Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007