F0004 on the ABB ACS355 is the “SHORT CIRC” fault. A fault stops the drive and lights its red LED. The drive will not run again until the fault is reset.
The drive detected a short between two output phases. It stops at once, because a phase-to-phase short drives current far beyond what the output stage can carry.
- Code
- F0004
- Type
- Fault (stops the drive)
- Drive
- ABB ACS355
- Kind of fault
- Output short circuit
01 / Causes
What causes F0004
- A short circuit in the motor cable or the motor.
- An internal fault in the drive, or high-frequency noise on the STO lines.
02 / Checks
What to check for F0004
In the order ABB gives them.
- 01Check the insulation of the motor and the motor cable, and check the motor winding.
- 02If the drive trips on overcurrent after a start command with no motor connected (try this in scalar control), the drive has an internal fault and needs replacing.
- 03Check the STO cabling and remove nearby sources of high-frequency noise.
Also in the manual
- Over a fieldbus, the drive reports this fault as code 2340.
03 / Clearing it
How to clear F0004
- Reset with the RESET key on the control panel, through a digital input or fieldbus, or by switching the supply off for a while. Parameter 1604 FAULT RESET SEL chooses the reset source. Once the cause is gone, the motor can be restarted.
- If the red LED on the drive is blinking rather than steady, the fault can only be reset by switching the drive's power off.
- Parameters 0401 LAST FAULT, 0412 PREVIOUS FAULT 1 and 0413 PREVIOUS FAULT 2 hold the three most recent faults, and 0404 to 0409 show the drive's operating data at the moment of the latest one.
Clear it once. If F0004 comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.
04 / On site
How output short circuit faults are traced on site
General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.
- 01Isolate and discharge, then disconnect the motor cable at the drive terminals.
- 02Measure phase to phase on the cable and on the motor separately, and insulation-test between phases.
- 03Inspect the motor terminal box for loose links, tracking or a burnt terminal board.
- 04Check that nothing between drive and motor (a contactor, isolator or junction box) has failed or been miswired.
05 / Repair
When F0004 means a repair
If the cable and motor are clear and the fault stays with nothing connected to the output, the drive's output stage has failed.
If F0004 keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on ABB drives, and they arrive knowing what to look for.
06 / Other drives
Output short circuit: the same fault on other drives
Each maker numbers this protection differently. Codes from each maker's own manual.
| Drive | Codes |
|---|---|
| Siemens SINAMICS G120 | F07807 Short-circuit detected |
| Allen-Bradley PowerFlex 525 | F041 Phase UV Short · F042 Phase UW Short · F043 Phase VW Short |
| Delta C2000 | occ IGBT short circuit between upper bridge and lower bridge |
| Delta ASDA-B2 | AL083 Servo drive outputs excessive current |
| Schneider Electric Altivar ATV320 | HDF IGBT desaturation error · SCF1 Motor short circuit error · SCF5 Motor short circuit error |
| INVT Goodrive20 (GD20) | OUt1 Inverter unit U phase protection · OUt2 Inverter unit V phase protection · OUt3 Inverter unit W phase protection |
| Yaskawa V1000 | SC IGBT Short Circuit |
| Yaskawa A1000 | SC Output Short Circuit or IGBT Fault |
| Yaskawa GA500 | SC Short Circuit/IGBT Failure |
| Siemens MICROMASTER 430 | F0022 Hardware monitoring active |
| INVT Goodrive200A (GD200A) | OUt1 Inverter unit U-phase protection · OUt2 Inverter unit V-phase protection · OUt3 Inverter unit W-phase protection |
| Danfoss VLT Micro Drive FC 51 | Alarm 16 Short circuit |
07 / More codes
Other ACS355 codes
Source
ABB, ACS355 user's manual, Rev E, effective 2 November 2020, 3AUA0000066143, Fault tracing.
Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of ABB and is not its authorised service partner.