C2000 occ: IGBT short circuit between upper bridge and lower bridge

occ on the Delta C2000 is the “IGBT short circuit between upper bridge and lower bridge” fault. A fault stops the drive's output. On over-current and over-voltage faults the drive closes its output gate at once and the motor coasts to a stop.

The drive detected a short between two output phases. It stops at once, because a phase-to-phase short drives current far beyond what the output stage can carry.

Code
occ
Type
Fault (stops the drive)
Drive
Delta C2000
Kind of fault
Output short circuit

01 / Causes

What causes occ

  • An IGBT failure.
  • A failure in the short-circuit detection circuit.

02 / Checks

What to check for occ

In the order Delta Electronics gives them.

  1. 01Check the motor wiring.
  2. 02Switch the power off and on. If occ is still there, Delta's instruction is to return the drive to the factory for repair.

Also in the manual

  • Fault ID 5. A short circuit between the upper and lower bridge of the IGBT module, caught by hardware protection. Reset manually, 5 seconds after the fault has cleared.

03 / Clearing it

How to clear occ

  • Remove the cause first. Then press STOP/RESET on the keypad, or switch on a multi-function input set to 5 (Reset).
  • Most faults can be reset 5 seconds after the fault has cleared. Over-voltage faults reset only once the DC bus is below 90% of the trip level, and overheating faults only once the temperature is 10°C below it.
  • Some faults can only be cleared by switching the power off: the current detection and hardware protection faults (cd1 to cd3, Hd0 to Hd3), the watchdog (WDTT), STO Loss (STL1 to STL3) and the CPU error (TRAP).
  • After resetting, if the keypad returns to its main page and shows no fault after ESC, the fault is cleared.

Clear it once. If occ comes straight back, stop resetting and find the cause: repeated resets on current and earth faults can turn a cable fault into a damaged drive.

04 / On site

How output short circuit faults are traced on site

General practice for this kind of fault on any drive, in the order a technician works. Isolate the supply and let the DC bus discharge before touching terminals.

  1. 01Isolate and discharge, then disconnect the motor cable at the drive terminals.
  2. 02Measure phase to phase on the cable and on the motor separately, and insulation-test between phases.
  3. 03Inspect the motor terminal box for loose links, tracking or a burnt terminal board.
  4. 04Check that nothing between drive and motor (a contactor, isolator or junction box) has failed or been miswired.

05 / Repair

When occ means a repair

If the cable and motor are clear and the fault stays with nothing connected to the output, the drive's output stage has failed.

If occ keeps returning, send the code, a photo of the drive's rating plate and what the machine was doing when it tripped to MachineryFix on WhatsApp or call +91 70133 33007. We match a technician who works on Delta drives, and they arrive knowing what to look for.

06 / Other drives

Output short circuit: the same fault on other drives

Each maker numbers this protection differently. Codes from each maker's own manual.

DriveCodes
Siemens SINAMICS G120F07807 Short-circuit detected
Allen-Bradley PowerFlex 525F041 Phase UV Short · F042 Phase UW Short · F043 Phase VW Short
ABB ACS355F0004 SHORT CIRC
Delta ASDA-B2AL083 Servo drive outputs excessive current
Schneider Electric Altivar ATV320HDF IGBT desaturation error · SCF1 Motor short circuit error · SCF5 Motor short circuit error
INVT Goodrive20 (GD20)OUt1 Inverter unit U phase protection · OUt2 Inverter unit V phase protection · OUt3 Inverter unit W phase protection
Yaskawa V1000SC IGBT Short Circuit
Yaskawa A1000SC Output Short Circuit or IGBT Fault
Yaskawa GA500SC Short Circuit/IGBT Failure
Siemens MICROMASTER 430F0022 Hardware monitoring active
INVT Goodrive200A (GD200A)OUt1 Inverter unit U-phase protection · OUt2 Inverter unit V-phase protection · OUt3 Inverter unit W-phase protection
Danfoss VLT Micro Drive FC 51Alarm 16 Short circuit

07 / More codes

Other C2000 codes

Source

Delta Electronics, C2000 Series User Manual, Issued edition 01, firmware V2.05 (2019-02-13), DELTA_IA-MDS_VFD-C2000_UM_EN_20190213, Chapter 14, Fault Codes and Descriptions.

Codes, names, causes and remedies are taken from that edition of the manual and reworded; nothing is added to them. Firmware and manual editions differ, so check your drive's own manual before changing parameters. MachineryFix is independent of Delta and is not its authorised service partner.

Written & reviewed by MachineryFix — last reviewed — questions? Call +91 70133 33007